BS 7609-1992+A2-2009 使用铜或铝导线的电力电缆用未绝缘压接或机械连接器的安装和检验的实施规程.pdf
《BS 7609-1992+A2-2009 使用铜或铝导线的电力电缆用未绝缘压接或机械连接器的安装和检验的实施规程.pdf》由会员分享,可在线阅读,更多相关《BS 7609-1992+A2-2009 使用铜或铝导线的电力电缆用未绝缘压接或机械连接器的安装和检验的实施规程.pdf(18页珍藏版)》请在三一文库上搜索。
1、BRITISH STANDARD Code of practice for Installation and inspection of uninsulated compression and mechanical connectors for power cables with copper or aluminium conductors ICS 29.120.20 BS 7609:1992 +A2:2009 This British Standard, having been prepared under the direction of the Cables and Insulation
2、 Standards Policy Committee, was published under the authority of the Standards Board and comes into effect on 15 October 1992 The following BSI references relate to the work on this standard: Committee reference CIL/20 Draft for comment 91/31861 DC Committees responsible for this British Standard T
3、he preparation of this British Standard was entrusted by the Cables and Insulation Standards Policy Committee (CIL/-) to Technical Committee CIL/20, upon which the following bodies were represented: Aluminium Federation Association of Consulting Engineers Association of Manufacturers of Domestic Ele
4、ctrical Appliances British Approvals Service for Cables British Cable Makers Confederation British Plastics Federation British Steel Industry British Telecommunications plc Department of the Environment (Property Services Agency) Department of Trade and Industry (Consumer Safety Unit, CA Division) E
5、lectricity Association Engineering Equipment and Materials Users Association Institution of Electrical Engineers London Regional Transport The following bodies were also represented in the drafting of the standard, through subcommittees and panels: Beccama (Beama Electrical Cable Connector and Acces
6、sories Manufacturers Association) Electrical Contractors Association Electrical Installation Equipment Manufacturers Association (BEAMA Ltd.) ERA Technology Ltd. Institution of Lighting Engineers London Underground Ltd. Transmission and Distribution Association (BEAMA Ltd.) Amendments issued since p
7、ublication Amd. No. DateComments 1644429 September 2006See foreword BSI 2008 ISBN 978 0 580 63230 3 Amendment 31 December 2008 See foreword No. 2 BS 7609:1992+A2:2009 i Contents Page Committees responsibleInside front cover Forewordii 1Scope1 2References1 3Definitions1 4Compression connectors1 5Mech
8、anical connectors8 6Bolting of terminal lugs to equipment8 7Tooling9 8Maintenance and certification of tooling9 Annex A (informative) Maintenance, testing and certification of tooling10 Figure 1 Illustrations of compression die sets3 Figure 2 Illustrations of bi-metallic connector3 Figure 3 Examples
9、 of correct and incorrect bolted termination4 Figure 4 Examples of correct and incorrect compression preparation5 Figure 5 Illustrations of three compression styles in use6 Figure 6 Examples of common compression faults7 Table 1 Recommended torque wrench settings for aluminium and copper termination
10、s9 List of referencesInside back cover BSI 2008 BS 7609:1992+A2:2009 ii Foreword This British Standard has been prepared under the direction of the Cables and Insulation Standards Policy Committee. BS 7609 is intended to give guidance to manufacturers and contractors who use compression and mechanic
11、al connectors to enable power cables to be terminated using good engineering practice and to provide quality control guidance for the tools which are used to install connectors. As a code of practice, this British Standard takes the form of guidance and recommendations. It should not be quoted as if
12、 it were a specification and particular care should be taken to ensure that claims of compliance are not misleading. Summary of pages This document comprises a front cover, an inside front cover, pages i and ii, pages 1 to 12, an inside back cover and a back cover. This standard has been updated (se
13、e copyright date) and may have had amendments incorporated. This will be indicated in the amendment table on the inside front cover. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British S
14、tandard cannot confer immunity from legal obligations. BSI 2008 BS 7609:1992+A2:2009 The start and finish of text introduced or altered by Amendments No. 1 and No.2 is indicated in the text by tags and . 1 1 Scope This British Standard recommends methods and procedures applicable for the installatio
15、n of uninsulated compression and mechanical connectors for use on copper or aluminium conductors of insulated cables conforming to BS EN 60228:2005 having a cross-sectional area equal to or greater than 10 mm2for copper and equal to or greater than 16 mm2for aluminium. 2 References 2.1 Normative ref
16、erences BS 7609 incorporates, by reference, provisions from specific editions of other publications. These normative references are cited at the appropriate points in the text and the publications are listed on the inside back cover. Subsequent amendments to, or revisions of, any of these publicatio
17、ns apply to this standard only when incorporated in it by updating or revision. 2.2 Informative references BS 7609 refers to other publications that provide information or guidance. Editions of these publications current at the time of issue of this standard are listed on the inside back cover, but
18、reference should be made to the latest editions. 3 Definitions For the purposes of this British Standard, the following definitions apply. 3.1 connector component or assembly of components designed to accept one or more conductor(s) for the purpose of making an electrical connection 3.2 mechanical c
19、onnector assembly designed to clamp conductors by mechanical screw force 3.3 insulation-piercing connector mechanical connector which does not require removal of the conductor insulation to make an electrical connection 3.4 compression connector component designed to make a connection by deformation
20、 of the barrel around the conductor NOTEThe term compression covers the term crimping. 3.5 barrel part of a connector designed to accommodate the conductor 3.6 palm part of a terminal lug formed flat to make a bolted connection to an equipment terminal 3.7 terminal lug connector comprising a palm an
21、d a barrel, for connecting a conductor to an equipment terminal 4 Compression connectors 4.1 Selection of connectors and associated compression dies Each connector should be clearly identified by a reference on the barrel or palm. This reference should enable the user to ascertain whether the fittin
22、g selected is of the correct size and type for the conductor(s) in question; it should also allow the correct die set and compression tool to be selected from the manufacturers recommended list. 4.2 Preparation of a conductor 4.2.1 General The insulation should be stripped back so that when assemble
23、d no insulation can be trapped in the barrel. Care should be taken whilst stripping the insulation to avoid damaging the conductor strands with the stripping tool. The exposed conductor should be cleaned to remove any particles of the insulation material. 4.2.2 Aluminium conductors Unless otherwise
24、stated by the connector manufacturer, the conductor should be thoroughly abraded both to remove surface oxide and create a rough surface to ensure good electrical contact. Suitable abrasives are aluminium oxide cloth Grade 80 or a stainless steel wire brush; separate brushes should be kept for coppe