1、 ATIS-0600307.2007 FIRE RESISTANCE CRITERIA - IGNITABILITY REQUIREMENTS FOR EQUIPMENT ASSEMBLIES, ANCILLARY NON-METALLIC APPARATUS, AND FIRE SPREAD REQUIREMENTS FOR WIRE AND CABLE A AMERICAN MERICAN N NATIONAL ATIONAL S STANDARD FOR TANDARD FOR T TELECOMMUNICATIONSELECOMMUNICATIONS The Alliance for
2、Telecommunication Industry Solutions (ATIS) is a technical planning and standards development organization that is committed to rapidly developing and promoting technical and operations standards for the communications and related information technologies industry worldwide using a pragmatic, flexib
3、le and open approach. Over 1,100 participants from over 300 communications companies are active in ATIS 22 industry committees and its Incubator Solutions Program. AMERICAN NATIONAL STANDARD Approval of an American National Standard requires review by ANSI that the requirements for due process, cons
4、ensus, and other criteria for approval have been met by the standards developer. Consensus is established when, in the judgment of the ANSI Board of Standards Review, substantial agreement has been reached by directly and materially affected interests. Substantial agreement means much more than a si
5、mple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that a concerted effort be made towards their resolution. The use of American National Standards is completely voluntary; their existence does not in any respect preclude anyone, whether
6、 he has approved the standards or not, from manufacturing, marketing, purchasing, or using products, processes, or procedures not conforming to the standards. The American National Standards Institute does not develop standards and will in no circumstances give an interpretation of any American Nati
7、onal Standard. Moreover, no person shall have the right or authority to issue an interpretation of an American National Standard in the name of the American National Standards Institute. Requests for interpretations should be addressed to the secretariat or sponsor whose name appears on the title pa
8、ge of this standard. CAUTION NOTICE: This American National Standard may be revised or withdrawn at any time. The procedures of the American National Standards Institute require that action be taken periodically to reaffirm, revise, or withdraw this standard. Purchasers of American National Standard
9、s may receive current information on all standards by calling or writing the American National Standards Institute. Notice of Disclaimer however, they must meet one of the other appropriate options contained in 4.1.2. See 4.1.1 and 4.1.2 regarding requirements for items such as plugs, sockets, jacks
10、, terminal blocks, etc., which may form part of an enclosure. Discrete (non-electrically energized) components with overall dimensions of 1/4 in (6.3 mm) x 1/4 in (6.3 mm) x 1/4 in (6.3 mm) or less, or constituting a fuel load of 1 g (0.035 oz) or less are exempt from the requirements of 4.1.2 and 4
11、.1.3. If such components are grouped in close proximity and their total mass exceeds 1 g (0.035 oz), they shall comply with 5.2. 4.1.4 Interconnect wire Individual interconnect wire and cable (copper and optic fiber) used within equipment assemblies shall satisfy the flammability requirements of VW-
12、1 as specified in ANSI/UL 1581. Any wire and cable exterior to an equipment assembly shall meet the requirements of 4.2. 4.2 Fire spread requirements for wire and cable The requirements in 4.2.1 through 4.2.3 apply to wire and cable, including communications cable, optical fiber cable, dc power wire
13、, and cable external to equipment assemblies. 5 -,-,- ATIS-0600307.2007 The requirements of 4.2 do not apply to OSP wire and cables. The requirements in 4.2.1 through 4.2.3 do not apply to compartmented cable entrance facilities. However, cables entering the CEF from the outside should be spliced to
14、 cables that comply with 4.2.1 through 4.2.3, as appropriate, as close as is practical to the point at which the cables enter the CEF. Wire and cable installations in hollow spaces, vertical shafts, and ventilation or air-handling ducts should be so made that the possible spread of fire or products
15、of combustion will not be substantially increased. All penetrations through fire-resistance rated walls, partitions, floors, or ceilings should be fire stopped using products tested to ANSI/UL 1479 (ASTM E 814), the requirements of the fire stop manufacturer and the requirements of the local model b
16、uilding code in force. 4.2.1 Ducts, plenums, or other space used for conditioned air Communications wire and cable shall have a maximum flame spread of 5 ft (1.52 m), a maximum peak optical density of 0.5, and a maximum average optical density of 0.15, when tested in accordance with ANSI/NFPA 262. E
17、xamples of cable types meeting these requirements are: CMP, CL2P, CL3P, OFNP, OFCP, MPP, FPLP, and CATVP. Power wire and cable shall comply with Article 300-22 of ANSI/NFPA 70. 4.2.2 Riser shafts Wire and cable in riser shafts shall comply with the requirements of ANSI/UL 1666. Examples of cable typ
18、es meeting these requirements are: CMR, CL2R, CL3R, OFNR, OFCR, MPR, FPLR, and CATVR, in addition to those specified in 4.2.1. 4.2.3 Other spaces Wire and cable used in spaces other than those covered by 4.2.1 and 4.2.2 shall comply with the requirements of the vertical-tray flame test per one of th