《BS-EN-1366-7-2004.pdf》由会员分享,可在线阅读,更多相关《BS-EN-1366-7-2004.pdf(60页珍藏版)》请在三一文库上搜索。
1、BRITISH STANDARD BS EN 1366-7:2004 Fire resistance tests for service installations Part 7: Conveyor systems and their closures The European Standard EN 1366-7:2004 has the status of a British Standard ICS 13.220.50 ? Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Unc
2、ontrolled Copy, (c) BSI BS EN 1366-7:2004 This British Standard was published under the authority of the Standards Policy and Strategy Committee on 8 July 2004 BSI 8 July 2004 ISBN 0 580 44018 4 National foreword This British Standard is the official English language version of EN 1366-7:2004. The U
3、K participation in its preparation was entrusted by Technical Committee FSH/22, Fire resistance tests, to Subcommittee FSH/22/5, Fire resistance testing of doors, which has the responsibility to: A list of organizations represented on this subcommittee can be obtained on request to its secretary. Cr
4、oss-references The British Standards which implement international or European publications referred to in this document may be found in the BSI Catalogue under the section entitled “International Standards Correspondence Index”, or by using the “Search” facility of the BSI Electronic Catalogue or o
5、f British Standards Online. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. aid enquirers to understand the text;
6、present to the responsible international/European committee any enquiries on the interpretation, or proposals for change, and keep the UK interests informed; monitor related international and European developments and promulgate them in the UK. Summary of pages This document comprises a front cover,
7、 an inside front cover, the EN title page, pages 2 to 57 and a back cover. The BSI copyright notice displayed in this document indicates when the document was last issued. Amendments issued since publication Amd. No.DateComments Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:
8、00 2006, Uncontrolled Copy, (c) BSI EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 1366-7 June 2004 ICS 13.220.50 English version Fire resistance tests for service installations - Part 7: Conveyor systems and their closures Essais de rsistance au feu des installations techniques - Partie 7: Fe
9、rmetures de passages pour convoyeurs et bandes transporteuses Feuerwiderstandsprfungen fr Installationen - Teil 7: Frderanlagen und ihre Abschlsse This European Standard was approved by CEN on 2 February 2004. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate
10、the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CEN member. This European Standard exists
11、in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official versions. CEN members are the national standards bodies
12、 of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR S
13、TANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: rue de Stassart, 36 B-1050 Brussels 2004 CENAll rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 1366-7:2004: E Licensed Copy: sheffieldun sheff
14、ieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 1366-7:2004 (E) 2 Contents page Foreword3 1 Scope 6 2 Normative references6 3 Terms and definitions .7 4 Test equipment 8 5 Test conditions 8 6 Test specimen12 7 Installation of test specimen 16 8 Conditioning.32 9 Applica
15、tion of instrumentation.33 10 Test procedure.47 11 Performance criteria48 12 Test report48 13 Field of direct application of test results 49 14 Classification51 Annex A (normative) Arrangement of unexposed thermocouples on closures for conveyor systems with non-rectangular shapes52 Annex B (normativ
16、e) Part configuration test specimen.53 B.1 General53 B.2 Changes to the penetrating components53 B.3 Large test specimen53 Annex C (informative) General guidance on the design of closure and conveyor system assemblies and their classification for self closing durability55 C.1 General55 C.2 Self clos
17、ing durability .55 C.3 General guidance for closure and conveyor system assemblies 56 Bibliography57 Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 1366-7:2004 (E) 3 Foreword This document (EN 1366-7:2004) has been prepared by Technical
18、Committee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by December 2004, and conflicting national standards shall be
19、 withdrawn at the latest by December 2004. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association. EN 1366 Fire resistance tests for service installations consists of the following parts: Part 1: Ducts Part 2: Fire dampers Part
20、 31): Penetration seals Part 41): Linear joint seals Part 5: Service ducts and shafts Part 61): Raised access floors and hollow floors Part 7: Conveyor systems and their closures Part 81): Smoke extraction ducts Part 91): Single compartment smoke extraction ducts Part 101): Smoke control dampers Par
21、t 111): Fire protective systems for essential services Annex A and annex B are normative and annex C is informative. 1) In course of preparation. Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 1366-7:2004 (E) 4 This document includes a B
22、ibliography. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Ital
23、y, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 1366-7:2004 (E) 5 Introduction This part of
24、 this European Standard was developed to provide a method of fire resistance testing for assessing the contribution of a closure for a conveyor system together with all its anchoring parts and the frame/guide included to the fire resistance of a separating element when penetrated by a conveyor syste
25、m including any relevant penetrating components. Caution The attention of all persons concerned with managing and carrying out this fire resistance test is drawn to the fact that fire testing may be hazardous and that there is a possibility that toxic and/or harmful smoke and gases may be evolved du
26、ring the test. Mechanical and operational hazards may also arise during the construction of the test elements or structures, their testing and disposal of test residues. An assessment of all potential hazards and risks to health should be made and safety precautions should be identified and provided
27、. Written safety instructions should be issued. Appropriate training should be given to relevant personnel. Laboratory personnel should ensure that they follow written safety instructions at all times. Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy,
28、 (c) BSI EN 1366-7:2004 (E) 6 1 Scope This part of this European Standard specifies a method of fire testing to determine the fire resistance of closure and conveyor system assemblies designed for installation within openings of separating elements, including any sealing necessary between the closur
29、e for a conveyor system and any penetrating components like conveyor tracks, electrical cables and pneumatic pipes being essential parts of the closure and conveyor system assembly together with the penetration seal. This part of European Standard is not applicable to other test methods required to
30、fully assess closures for conveyor systems, e.g. test methods to evaluate the serviceability and reliable functioning of interconnected systems. The fire testing of fire dampers for heating and ventilation systems, fire doors and shutters for normal traffic paths and the movement of liquid and combu
31、stible gas, are specifically excluded from this European Standard. This European Standard is read in conjunction with EN 1363-1. In the absence of any European Technical Specification for closure and conveyor system assemblies, this European Standard gives advice on the classification of durability
32、for closure and conveyor system assemblies. 2 Normative references This European Standard incorporates by dated or undated reference, provisions from other publications. These normative references are cited at the appropriate places in the text, and the publications are listed hereafter. For dated r
33、eferences, subsequent amendments to or revisions of any of these publications apply to this European Standard only when incorporated in it by amendment or revision. For undated references the latest edition of the publication referred to applies (including amendments). prEN 520, Gypsum plasterboards
34、 Definitions, requirements and test methods. EN 1191, Windows and doors Resistance to repeated opening and closing Test method. EN 1363-1, Fire resistance tests Part 1: General requirements. EN 1363-2, Fire resistance tests Part 2: Alternative and additional procedures prEN 1366-3, Fire resistance t
35、ests for service installations Part 3: Penetration seals. EN 1634-1, Fire resistance tests for door and shutter assemblies Part 1: Fire doors and shutters. EN 12605, Industrial, commercial and garage doors and gates Mechanical aspects Test methods. EN 13501-2, Fire classification of construction pro
36、ducts and building elements Part 2: Classification using data from fire resistance tests, excluding ventilation services. EN ISO 13943, Fire safety Vocabulary (ISO 13943:2000). Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 1366-7:2004 (
37、E) 7 3 Terms and definitions For the purposes of this European Standard, the terms and definitions given in EN 1363-1, prEN 1366-3, EN 1634-1, EN ISO 13943 together with the following apply. 3.1 anchoring means of attachment of the closure for the conveyor system to the various components of the sup
38、porting or associated supporting construction to ensure correct functioning 3.2 associated supporting construction specific construction in which the closure and conveyor system assembly is to be installed in practice and which is used to close off the furnace and provide the levels of restraint and
39、 thermal heat transfer to be experienced in normal use 3.3 clearing device device which is generally part of the conveyor system used to clear the closure area of transportable goods during shutting of the closure for the conveyor system 3.4 closing device device to be attached to a closure for a co
40、nveyor system which provides a return to closed condition NOTE The closing device ensures that the closure for the conveyor system is closed from any open position. 3.5 closure and conveyor system assembly complete assembly of the closure for the conveyor system and, where relevant, its frame or gui
41、de, which is provided for closing off a permanent opening in a separating element. This includes the anchoring parts for the connection with the separating element, a length of any penetrating component on either side of the construction and the penetration seal, any sealing system between the closu
42、re for a conveyor system, the conveyor system and any closing and/or separating device 3.6 closure area vicinity at the opening which needs to be cleared in order to permit the shutting of the closure for the conveyor system 3.7 closure for a conveyor system device to shut an opening for a conveyor
43、system within a fire separating element NOTE A closure for a conveyor system includes any component used to close the opening e.g. frames, guide rails, pivoting flaps, fittings and interlocking devices. 3.8 conveyor system arrangement used to transport materials through an opening in a fire separati
44、ng element NOTE This can be conveyor tracks, remotely controlled or automatic equipment. 3.9 conveyor track arrangement that guides the items to be transported NOTE This can be e.g. belts, slides, rails, screws, chains and ducts or pipes in which airborne particles are moved. Licensed Copy: sheffiel
45、dun sheffieldun, na, Sun Oct 29 09:35:37 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 1366-7:2004 (E) 8 3.10 penetration aperture in a separating element for the passage of a penetrating component 3.11 penetrating component elements such as cables, pneumatic and/or hydraulic pipes and the conveyor
46、system which pass through the separating element and which may influence the performance of a closure for the conveyor system in relation to its fire resistance 3.12 penetration seal system used to maintain the fire resistance of a separating element at the position where there is provision for pene
47、trating components (e.g. essential parts of conveyor system, conduits, electrical cables and pipes) to pass through the fire separating element 3.13 separating device arrangement used to separate a continuous conveyor system penetrating an opening in a fire resisting separating element to allow a cl
48、osure to fully advance to its closed position 3.14 standard supporting construction form of construction of known fire resistance used to close off the furnace and support the test specimen being evaluated 3.15 test specimen complete closure and conveyor system assembly which is to be installed in a
49、 standard or associated supporting construction to allow it to be evaluated 4 Test equipment The test equipment specified in EN 1363-1, and if applicable EN 1363-2, shall be used. 5 Test conditions 5.1 Heating conditions The heating conditions and the furnace atmosphere shall conform to those given in EN 1363-1, or if applicable, EN 1363-2. NOTE In the presence of any intumescent material used for the test specimen, requirements may exist to apply in addition to the standard temp