《BS-EN-1366-3-2009.pdf》由会员分享,可在线阅读,更多相关《BS-EN-1366-3-2009.pdf(108页珍藏版)》请在三一文库上搜索。
1、BS EN 1366-3:2009 ICS 13.220.50 NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW BRITISH STANDARD Fire resistance tests for service installations Part 3: Penetration seals Licensed CopyChinese University of Hong Kong, 11/04/2009 07:18, Uncontrolled Copy, (c) BSI This British St
2、andard was published under the authority of the Standards Policy and Strategy Committee on 31 March 2009 BSI 2009 ISBN 978 0 580 57464 1 Amendments/corrigenda issued since publication DateComments BS EN 1366-3:2009 National foreword This British Standard is the UK implementation of EN 1366-3:2009. I
3、t supersedes BS EN 1366-3:2004 which is withdrawn. The UK participation in its preparation was entrusted to Technical Committee FSH/22/3, Test procedures for fire penetration and seals. A list of organizations represented on this committee can be obtained on request to its secretary. This publicatio
4、n does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard cannot confer immunity from legal obligations. Licensed CopyChinese University of Hong Kong, 11/04/2009 07:18, Uncontrolled Copy, (c) BSI BS
5、 EN 1366-3:2009 EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 1366-3 February 2009 ICS 13.220.50Supersedes EN 1366-3:2004 English Version Fire resistance tests for service installations - Part 3: Penetration seals Essais de rsistance au feu des installations techniques - Partie 3 : Calfeutrem
6、ents de trmies Feuerwiderstandsprfungen fr Installationen - Teil 3: Abschottungen This European Standard was approved by CEN on 3 January 2009. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a n
7、ational standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version
8、in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmar
9、k, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATI
10、ON EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2009 CENAll rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 1366-3:2009: E Licensed CopyChinese University of Hong Kong, 11/04/2009 07:18, Uncontrolled
11、Copy, (c) BSI BS EN 1366-3:2009 EN 1366:2009 (E) 2 Contents Page Foreword . 4 Introduction 5 1 Scope 6 2 Normative references . 6 3 Terms and definitions . 8 4 Test equipment 11 5 Test conditions 11 5.1 Heating conditions 11 5.2 Pressure conditions 11 6 Test specimen . 12 6.1 Size and distances 12 6
12、.2 Number . 12 6.3 Design 12 6.4 Construction 15 6.5 Verification . 15 7 Installation of test specimen 15 7.1 General . 15 7.2 Supporting construction 15 7.3 Installation of service(s) . 17 7.4 Installation of penetration seal 17 7.5 Multiple penetration seals in one test specimen . 17 8 Conditionin
13、g 17 9 Application of instrumentation 17 9.1 Thermocouples . 17 9.2 Integrity measurement 19 9.3 Pressure . 19 10 Test procedure 19 10.1 General . 19 10.2 Integrity 19 10.3 Other observations . 19 11 Performance criteria . 20 11.1 Integrity 20 11.2 Insulation . 20 11.3 Multiple penetrations 20 12 Te
14、st report . 20 13 Field of direct application of test results 20 13.1 Orientation . 20 13.2 Supporting construction 21 13.3 Services . 21 13.4 Service support construction 22 13.5 Seal size and distances 22 Annex A (normative) Standard configuration for large cable penetration seals . 26 A.1 Structu
15、re of specimens 26 A.2 Non-standard configuration . 28 Licensed CopyChinese University of Hong Kong, 11/04/2009 07:18, Uncontrolled Copy, (c) BSI BS EN 1366-3:2009 EN 1366-3:2009 (E) 3 A.3 Field of direct application 28 Annex B (normative) Standard configuration for small cable penetration seals 42
16、B.1 Structure of specimens 42 B.2 Field of direct application 43 B.3 Non-standard configuration . 44 Annex C (normative) Standard configuration and field of direct application for modular systems and cable boxes . 49 C.1 Modular Systems 49 C.2 Cable boxes . 51 C.3 Non-standard configuration . 52 Ann
17、ex D (normative) Specimen design and field of direct application for bus bars 56 D.1 Structure of specimens 56 D.2 Field of direct application 56 D.3 Non-standard configuration . 56 Annex E (normative) Standard configuration and field of direct application for pipe penetration seals . 58 E.1 Standar
18、d configuration for penetration seals for pipes according to 6.3.2 a) “metal pipes“ . 58 E.2 Standard configuration for penetration seals for pipes according to 6.3.2 d) “plastic pipes“ . 61 E.3 Trunking and conduits . 65 E.4 Standard configuration for floor penetrations ending at floor level (e.g.
19、floor drain) . 66 Annex F (normative) Standard configuration and field of direct application for large mixed penetration seals . 74 F.1 General . 74 F.2 Standard Mixed Module 74 F.3 Standard configuration for combinations of type a) according to F.1.2 . 76 F.4 Standard configuration for combinations
20、 of type b), c) and d) according to F.1.2 76 F.5 Field of direct application 77 Annex G (normative) Critical pipe/cable approach . 84 G.1 General . 84 G.2 Definition of “critical“ . 84 G.3 Procedure selecting critical pipes from previous test data 84 G.4 Procedure selecting critical cables from prev
21、ious test data 85 Annex H (informative) Explanatory notes 87 H.1 General . 87 H.2 Notes on the scope and application of test results . 87 H.3 Notes on test conditions 92 H.4 Notes on test construction 92 H.5 Notes on test procedure . 102 H.6 Notes on test criteria 102 H.7 Notes on validity of test r
22、esults (field of application) . 102 H.8 Notes on test report 103 Bibliography . 104 Licensed CopyChinese University of Hong Kong, 11/04/2009 07:18, Uncontrolled Copy, (c) BSI BS EN 1366-3:2009 EN 1366:2009 (E) 4 Foreword This document (EN 1366:2009) has been prepared by Technical Committee CEN/TC 12
23、7 “”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by August 2009, and conflicting national standards shall be withdrawn at the latest by August 2009. Atte
24、ntion is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 1366-3:2004. This document has been prepared under a mandate g
25、iven to CEN by the European Commission and the European Free Trade Association. Annexes A to G are normative. Annex H is informative. EN 1366, Fire resistance tests for service installations consists of the following: Part 1: Ducts Part 2: Fire dampers Part 3: Penetration seals Part 4: Linear joint
26、seals Part 5: Service ducts and shafts Part 6: Raised access floors and hollow floors Part 7: Conveyors systems and their closures Part 8: Smoke extraction ducts Part 9: Single compartment smoke extraction ducts Part 10: Smoke control dampers (in course of preparation) Part 11: Protective systems fo
27、r essential services (in course of preparation) According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Ger
28、many, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Licensed CopyChinese University of Hong Kong, 11/04/2009 07:18, Uncontrolled Copy, (c) BSI BS E
29、N 1366-3:2009 EN 1366-3:2009 (E) 3 Introduction This part of this European Standard has been prepared to provide a method of test for assessing the contribution of a penetration seal to the fire resistance of separating elements when they have been penetrated by a service or services. CAUTION The at
30、tention of all persons concerned with managing and carrying out this fire resistance test is drawn to the fact that fire testing may be hazardous and that there is a possibility that toxic and/or harmful smoke and gases may be evolved during the test. Mechanical and operational hazards may also aris
31、e during the construction of the test elements or structures, their testing and disposal of test residues. An assessment of all potential hazards and risks to health should be made and safety precautions should be identified and provided. Written safety instructions should be issued. Appropriate tra
32、ining should be given to relevant personnel. Laboratory personnel should ensure that they follow written safety instructions at all times. Licensed CopyChinese University of Hong Kong, 11/04/2009 07:18, Uncontrolled Copy, (c) BSI BS EN 1366-3:2009 EN 1366:2009 (E) 6 1 Scope This Part of EN 1366 spec
33、ifies a method of test and criteria for the evaluation (including field of application rules) of the ability of a penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a service. Penetration seals used to seal gaps around chimneys
34、, air ventilation systems, fire rated ventilation ducts, fire rated service ducts, shafts and smoke extraction ducts are excluded from this standard except for mixed penetration seals. The fire resistance of those services itself cannot be assessed with the methods described in this standard. Suppor
35、ting constructions are used in this standard to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating element into which the sealing system is to be installed in practice. This European Standard is used in conjunction with
36、EN 1363-1. The purpose of this test described in this standard is to assess: a) the effect of such penetrations on the integrity and insulation performance of the separating element concerned; b) the integrity and insulation performance of the penetration seal; c) the insulation performance of the p
37、enetrating service or services, and where necessary, the integrity failure of a service. No information can be implied by the test concerning the influence of the inclusion of such penetrations and sealing systems on the loadbearing capacity of the separating element. It is not the intention of this
38、 test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena are only to be noted in describing the general behaviour of test specimens during the test. This test is not intended to supply any information on
39、the ability of the penetration seal to withstand stress caused by movements or displacements of the penetrating services. The risk of spread of fire downwards caused by burning material, which drips through a pipe downwards to floors below, cannot be assessed with this test. Explanatory notes to thi
40、s test method are given in Annex H. All dimensions given without tolerances are nominal ones unless otherwise stated. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated re
41、ferences, the latest edition of the referenced document (including any amendments) applies. EN 520, Gypsum plasterboards Definitions, requirements and test methods EN 1329-1, Plastics piping systems for soil and waste discharge (low and high temperature) within the building structure Unplasticized p
42、oly(vinyl chloride) (PVC-U) Part 1: Specifications for pipes, fittings and the system EN 1363-1:1999, Fire resistance tests Part 1: General requirements Licensed CopyChinese University of Hong Kong, 11/04/2009 07:18, Uncontrolled Copy, (c) BSI BS EN 1366-3:2009 EN 1366-3:2009 (E) 3 EN 1363-2, Fire r
43、esistance tests Part 2: Alternative and additional procedures EN 1452-1, Plastics piping systems for water supply Unplasticized poly(vinyl chloride) (PVC-U) Part 1: General EN 1453-1, Plastics piping systems with structured wall-pipes for soil and waste discharge (low and high temperature) inside bu
44、ildings Unplasticized poly(vinyl chloride) (PVC-U) Part 1: Specifications for pipes and the system EN 1455-1, Plastics piping systems for soil and waste discharge (low and high temperature) within the building structure Acrylonitrile-butadiene-styrene (ABS) Part 1: Requirements for pipes, fittings a
45、nd the system EN 1519-1, Plastics piping systems for soil and waste discharge (low and high temperature) within the building structure Polyethylene (PE) Part 1: Specifications for pipes, fittings and the system EN 1565-1, Plastics piping systems with structured-wall pipes for soil and waste discharg
46、e (low and high temperature) inside buildings Styrene copolymer blends (SAN+PVC) Part 1: Specifications for pipes, fittings and the system EN 1566-1, Plastics piping systems for soil and waste discharge (low and high temperature) within the building structure Chlorinated poly(vinyl chloride) (PVC-C)
47、 Part 1: Specifications for pipes, fittings and the system EN 1992-1-2, Eurocode 2 Design of concrete structures Part 1-2: General rules Structural fire design EN 1996-1-2, Eurocode 6 Design of masonry structures Part 1-2: General rules Structural fire design EN 10305-4, Steel tubes for precision ap
48、plications Technical delivery conditions Part 4: Seamless cold drawn tubes for hydraulic and pneumatic power systems EN 10305-6, Steel tubes for precision applications Technical delivery conditions Part 6: Welded cold drawn tubes for hydraulic and pneumatic power systems EN 12201-2, Plastics piping
49、systems for water supply Polyethylene (PE) - Part 2: Pipes EN 12449, Copper and copper alloys Seamless, round tubes for general purposes EN 12666-1, Plastics piping systems for non-pressure underground drainage and sewerage Polyethylene (PE) Part 1: Specifications for pipes, fittings and the system EN 13501-1, Fire classification of construction products and building elements Part 1: Classification using test data from reaction to fire tests EN 13501-2, Fire classification of construction products and
链接地址:https://www.31doc.com/p-3739165.html