1、BRITISH STANDARD BS EN 13160-4:2003 Leak detection systems Part 4: Liquid and/or vapour sensor systems for use in leakage containments or interstitial spaces The European Standard EN 13160-4:2003 has the status of a British Standard ICS 23.020.01; 23.040.99; 29.260.20 ? Licensed Copy: sheffieldun sh
2、effieldun, na, Sun Oct 29 09:56:36 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS EN 13160-4:2003 This British Standard, was published under the authority of the Standards Policy and Strategy Committee on 16 June 2003 BSI 16 June 2003 ISBN 0 580 42077 9 National foreword This British Standard is the
3、official English language version of EN 13160-4:2003. The UK participation in its preparation was entrusted by Technical Committee PVE/21, Fabricated metallic tanks and equipment for storage tanks and filling stations, to Subcommittee PVE/21/2/2, Leak detection devices, which has the responsibility
4、to: A list of organizations represented on this subcommittee can be obtained on request to its secretary. Cross-references The British Standards which implement international or European publications referred to in this document may be found in the BSI Catalogue under the section entitled “Internati
5、onal Standards Correspondence Index”, or by using the “Search” facility of the BSI Electronic Catalogue or of British Standards Online. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a Britis
6、h Standard does not of itself confer immunity from legal obligations. aid enquirers to understand the text; present to the responsible European committee any enquiries on the interpretation, or proposals for change, and keep the UK interests informed; monitor related international and European devel
7、opments and promulgate them in the UK. Summary of pages This document comprises a front cover, an inside front cover, the EN title page, pages 2 to 21 and a back cover. The BSI copyright date displayed in this document indicates when the document was last issued. Amendments issued since publication
8、Amd. No. DateComments Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:56:36 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 13160-4 May 2003 ICS 23.020.01; 23.040.99; 29.260.20 English version Leak detection systems - Part 4: Liquid and/or va
9、pour sensor systems for use in leakage containments or interstitial spaces Systmes indicateurs de fuites - Partie 4: Systmes de dtection de liquide et/ou gaz dans des espaces de confinement ou des espaces interstitiels Leckanzeigesysteme - Teil 4: Flssigkeits- und/oder Gassensorensysteme in Leckage
10、oder berwachungsrumen This European Standard was approved by CEN on 10 March 2003. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and
11、 bibliographical references concerning such national standards may be obtained on application to the Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibilit
12、y of a CEN member into its own language and notified to the Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malt
13、a, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: rue de Stassart, 36 B-1050 Brussels 2003 CENAll rights of exploitation in any form and by
14、 any means reserved worldwide for CEN national Members. Ref. No. EN 13160-4:2003 E Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:56:36 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 13160-4:2003 (E) 2 Contents page Foreword3 1Scope 3 2Normative references 3 3Terms and definitions4 4Genera
15、l4 5Interstitial space.4 6Leakage containment 4 7Liquid sensor5 8Vapour sensor5 9Leak indicating device.5 10Type test of the liquid sensors.5 10.1Test objective.5 10.2Evaluation.5 10.3Test equipment 6 10.4Test method6 10.5Test results.8 10.6Sensor marking8 11Type test of discriminating liquid sensor
16、s8 11.1Discriminating liquid sensors for bulk quantities of stored product and water.8 11.2Discriminating liquid sensors for detection of thin films of stored product on water.11 12Type test of vapour sense.14 12.1Test objective.14 12.2Evaluation.14 12.3Test equipment 15 12.4Test method17 12.5Test r
17、eport 18 12.6Sensor marking19 13Type test of submerged vapour sensors 19 13.1Test objective.19 13.2Evaluation.19 13.3Test equipment 19 13.4Test method20 13.5Test result.21 Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:56:36 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 13160-4:2003 (E) 3
18、 Foreword This document (EN 13160-4:2003) has been prepared by Technical Committee CEN /TC 221, “Shop fabricated metallic tanks and equipment for storage tanks and for service stations“, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard,
19、 either by publication of an identical text or by endorsement, at the latest by November 2003, and conflicting national standards shall be withdrawn at the latest by November 2003. This European Standard consists of 7 parts: Leak detection systems; Part 1:General principles Part 2:Pressure and vacuu
20、m systems Part 3:Liquid systems for tanks Part 4:Liquid and/or vapour sensor systems for use in leakage containments or interstitial spaces Part 5:Tank gauge leak detection systems Part 6:Sensors in monitoring wells Part 7:General requirements and test methods for interstitial spaces, leak protectin
21、g linings and leak protecting jackets According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Irela
22、nd, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and the United Kingdom. 1 Scope This European Standard specifies the requirements for leak detection systems - class III for use in the interstitial space of double-skin systems or in leakage containmen
23、ts of single skin systems designed for water polluting fluids. This European Standard is not applicable to leak detection systems using non re-usable sensors. 2 Normative references This European Standard incorporates by dated or undated reference, provisions from other publications. These normative
24、 references are cited at the appropriate places in the text, and the publications are listed hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to this European Standard only when incorporated in it by amendment or revision. For undated referenc
25、es the latest edition of the publication referred to applies (including amendments). EN 131601:2003, Leak detection systems Part 1: General principles. EN 131607, Leak detection systems Part 7: General requirements and test methods for interstitial spaces, leak protecting linings and leak protecting
26、 jackets. Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:56:36 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 13160-4:2003 (E) 4 3 Terms and definitions For the purposes of this European Standard, the terms and definitions given in EN 13160-1:2003 apply. 4 General General principles accord
27、ing to EN 13160-1. Where the requirement is for low temperature performance the alternative test temperature is shown in brackets . Liquid or vapour sensors shall be installed in such a way that they can detect specific liquids or their vapours present in or entering the leakage containment or inter
28、stitial space. The leakage containment can take the form of a ? sump or riser containing spills from leaks in double wall lines or pumps; ? bund, designed to contain leakage from a storage tank or from any other facility containing liquids; ? other facilities in which sensors can be installed to det
29、ect the presence of liquids or vapours. 5 Interstitial space General requirements concerning the interstitial space according to EN 131607. The design of the interstitial space intended to detect liquid shall allow detection of a minimum amount of 10 l of a specific liquid present in or entering the
30、 interstitial space. The interstitial space shall allow an installation of the sensor at the deepest point of the interstitial space. The interstitial space shall be constructed so that the leakage liquid shall reach the deepest point of the interstitial space. For a tank, the system shall be design
31、ed so that there are no connections to the inner tank through the interstitial space, below the maximum filling level. For a pipe, the system shall be designed so that there are no connections to the inner pipe through the interstitial space. The interstitial space shall be capable of being tested f
32、or integrity. 6 Leakage containment The design of leakage containment intended to detect liquid shall allow detection of a minimum amount of 10 l of a specific liquid present in or entering the containment. The number of sensors of the system shall correspond to the intended number of low points in
33、the leakage containment. NOTEThe design of a leakage containment should allow that liquid leaking from any point in the primary system will collect in at least one of a number of low points in the leakage containment. The leakage containment shall be liquid tight and impervious to the stored product
34、, water or any other substance with which it is likely to come into contact, and shall have no outlets below the level of the maximum contained volume. If protection against ingress of water is not possible, technical measures have to be taken to avoid impairment of the function of the leak detector
35、. Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:56:36 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 13160-4:2003 (E) 5 No penetrations through the walls of the leakage containment shall be made which might interfere with its functions as leakage containment. It shall be possible to test
36、the leakage containment for leaks. If the leakage containment is used as a bund for a primary system holding liquids then the walls of the bund shall fully surround the system and shall be capable of containing the entire contents of the primary system. 7 Liquid sensor Liquid sensors shall detect sp
37、ecific liquids they can normally come into contact with (e. g. stored product, water). Liquid sensors shall comply with the test criteria according to clauses 10 or 11, as appropriate. 8 Vapour sensor Vapour sensors shall detect specific vapours from stored products. Vapour sensors shall comply with
38、 the test criteria according to clause 12. 9 Leak indicating device A leak indicating device shall be provided. An alarm shall indicate when the presence of stored product and/or water is detected. 10 Type test of the liquid sensors 10.1 Test objective The aim of the test is to verify the suitabilit
39、y of a sensor system to detect the ingress of liquid into the interstitial space or leakage containment, where this space is normally dry. Tests shall be performed to verify: ? the response time of the sensor system in indicating the presence of liquid, where the liquid level is rising at a given ra
40、te; ? the recovery time of the sensor system from a liquid-indicating condition following its removal from the presence of liquid. A sensor system shall be qualified for use with each type of liquid that it shall be required to detect. Where possible, tests shall be performed using these actual liqu
41、ids, however where significant hazards may result, a less harmful test liquid may be used having similar chemical and physical properties. For example, a substitute for petroleum spirit would be petroleum naphtha (an aliphatic petroleum distillate). 10.2 Evaluation Tests shall be deemed to have been
42、 passed where: ? the presence of liquids is not indicated when no liquid is present; ? the presence of liquid is indicated within 30 min after liquid is first introduced into the test system at the rate of 10 l/h; ? the presence of liquid is indicated within 6 min after liquid is first introduced in
43、to the test system at the rate of 50 l/h; Licensed Copy: sheffieldun sheffieldun, na, Sun Oct 29 09:56:36 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 13160-4:2003 (E) 6 ? the sensor has a measurable recovery time of max 20 h after removal of the test liquid. These criteria shall be satisfied over
44、the range of environmental conditions specified in the test in 10.4. The system shall remain in the alarm condition until the sensor has recovered and the alarm has been reset. 10.3 Test equipment A test vessel in the form of a flat-bottomed vertical cylinder, having a horizontal cross-sectional are
45、a of (0,1 0,002) m2 (i.e. a liquid depth of 0,01 m corresponds to a volume of 1 l) and a minimum depth of 0,6 m. One or more fittings flush with the inside surface of the vessel shall be provided in the floor of the vessel for the introduction of liquids. A similar fitting shall be provided having a
46、 drain cock capable of emptying the vessel at a rate of 5 l/min. Suitable quantities of each liquid for qualification (or suitable test liquids). A calibrated metering pump (with a reservoir of minimum 6 l capacity) capable of delivering liquid into the test vessel, at the rates specified in 10.2, w
47、ith an accuracy of 2 %. An environmental chamber the temperature of which can be varied over the range from - 25 ?C to + 70 ?C with an accuracy of 2 K. For the test in a temperature range from 40 C to + 40 C an environmental chamber the temperature of which can be varied over a range from 50 C to +
48、40 C with an accuracy of 2 K. A stop clock having a time indication in steps of 1 s to a minimum total of 24 h, with an accuracy of 2 s. 10.4 Test method 10.4.1Preparation The sensor under test shall befixed in its normal orientation ensuring contact with the floor of the test vessel but away from a
49、ny ports for the entry or extraction of liquid. The manufacturers fittings should be used wherever possible. The test vessel and metering pump reservoir shall be mounted inside the environmental chamber. The sensor under test shall be connected to the leak indicating device which shall be mounted outside the environmental chamber in ambient laboratory conditions. Prior to the series of tests for each liquid for which the sensor system shall be qualified, the metering p