1、BS EN 15092:2008 ICS 91.140.60 NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW BRITISH STANDARD Building valves Inline hot water supply tempering valves Tests and requirements Licensed Copy: London South Bank University, South Bank University, 16/11/2008 11:27, Uncontrolled Co
2、py, (c) BSI This British Standard was published under the authority of the Standards Policy and Strategy Committee on 30 September 2008 BSI 2008 ISBN 978 0 580 54889 5 Amendments/corrigenda issued since publication DateComments BS EN 15092:2008 National foreword This British Standard is the UK imple
3、mentation of EN 15092:2008. The UK committee would like to draw attention to the following concerns: 1.Subclause 7.6.2 requires that flow changes be accomplished within 10,5 seconds. This necessitates that valve 5 shown in Annex B is more than a simple on/off control. 2.The acoustic test in Subclaus
4、e 8.2 references EN ISO 3822. This requires the test to be conducted with cold water at both inlets; therefore arrangements need to be made to enable adjustment of the temperature setting of the valve over the whole range in order to satisfy the requirements of EN ISO 3822 and Subclause 8.2. 3.Annex
5、es A and B are informative, yet there are several references to these Annexes within Clause 7. This could result in irreproducibility, and inconsistencies in certifications. The UK participation in its preparation was entrusted to Technical Committee B/504/7, Valves and fittings for buildings. A lis
6、t of organizations represented on this committee can be obtained on request to its secretary. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard cannot confer immunity from leg
7、al obligations. Licensed Copy: London South Bank University, South Bank University, 16/11/2008 11:27, Uncontrolled Copy, (c) BSI BS EN 15092:2008 EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 15092 June 2008 ICS 91.140.60 English Version Building valves - Inline hot water supply tempering val
8、ves - Tests and requirements Robinetterie des btiments - Vannes mlangeuses en ligne dalimentation en eau chaude - Essais et exigences Gebudearmaturen - Thermostatische Mischer fr Warmwasserbereiter - Prfungen und Anforderungen This European Standard was approved by CEN on 29 May 2008. CEN members ar
9、e bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to
10、the CEN Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the sam
11、e status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, R
12、omania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: rue de Stassart, 36 B-1050 Brussels 2008 CENAll rights of exploitation in any form and by any means reser
13、ved worldwide for CEN national Members. Ref. No. EN 15092:2008: E Licensed Copy: London South Bank University, South Bank University, 16/11/2008 11:27, Uncontrolled Copy, (c) BSI BS EN 15092:2008 EN 15092:2008 (E) 2 Contents Page Foreword3 Introduction.4 1 Scope 5 2 Normative references5 3 Terms and
14、 definitions .6 4 Materials and surface finishes .7 4.1 General7 4.2 Nature of materials 7 5 Design and dimensional requirements .8 5.1 Backflow prevention8 5.2 Dimensional characteristics.8 5.3 Set temperature adjustment.10 5.4 Temperature override function.10 6 Mechanical tests and requirements.10
15、 6.1 Body strength test.10 6.2 Bending moment test for tempering valves10 6.3 Torque tests for temperature stops.11 7 Performance tests and requirements12 7.1 General12 7.2 Standard test conditions.12 7.3 Verification of valve temperature settings13 7.4 Determination of minimum flow rate .14 7.5 Tes
16、t for temperature stability starting from ambient.16 7.6 Test for temperature stability with changing flow rates17 7.7 Test for thermal shutoff with cold water supply failure.18 7.8 Test for temperature stability with changing inlet pressure.18 7.9 Test for temperature stability with changing inlet
17、temperature .19 7.10 Endurance test on the thermostat .20 8 Acoustic tests and requirements.21 8.1 General21 8.2 Test method21 8.3 Expression of results 21 8.4 Requirements.21 9 Classification21 10 Designation 21 11 Marking.22 11.1 Temperature marking22 11.2 Flow marking22 11.3 Identification markin
18、g .22 12 Instructions 22 Annex A (informative) Apparatus for endurance test on thermostat.24 Annex B (informative) Apparatus for performance test26 Annex C (normative) Measurement of parameters28 Annex D (informative) Temperature transient requirements29 Bibliography30 Licensed Copy: London South Ba
19、nk University, South Bank University, 16/11/2008 11:27, Uncontrolled Copy, (c) BSI BS EN 15092:2008 EN 15092:2008 (E) 3 Foreword This document (EN 15092:2008) has been prepared by Technical Committee CEN/TC 164 “Water supply”, the secretariat of which is held by AFNOR. This European Standard shall b
20、e given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by December 2008, and conflicting national standards shall be withdrawn at the latest by December 2008. Attention is drawn to the possibility that some of the elements of this docum
21、ent may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: A
22、ustria, Belgium, Bulgaria, Cyprus, Czech Repub- lic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Lice
23、nsed Copy: London South Bank University, South Bank University, 16/11/2008 11:27, Uncontrolled Copy, (c) BSI BS EN 15092:2008 EN 15092:2008 (E) 4 Introduction In respect of potential adverse effect on the quality of water intended for human consumption, caused by the product covered by this European
24、 Standard: a) this European Standard provides no information as to whether the product may be used without restric- tion in any of the Member States of the EU or EFTA; b) it should be noted that, while awaiting the adoption of verifiable European criteria, existing national regu- lations concerning
25、the use and/or the characteristics of this product remain in force. Licensed Copy: London South Bank University, South Bank University, 16/11/2008 11:27, Uncontrolled Copy, (c) BSI BS EN 15092:2008 EN 15092:2008 (E) 5 1 Scope This European Standard specifies dimensions, materials and performance req
26、uirements (including methods of test) for in line hot water supply tempering valves for sanitary hot water systems, of nominal sizes from DN 15 to DN 50. Tempering valves reduce the temperature of sanitary hot water for distribution throughout the hot water system. The conditions of use are specifie
27、d in Table 1. The valves are intended to be used with storage water heaters to provide tempered hot water to the terminal fitting. They are not intended to control the temperature at the point of use. Tempering valves control the distribution temperature from a water heater to a preset value or an a
28、djustable range, both between 45 C and 65 C. Table 1 Conditions of use Limits of use Recommended limits for operation Dynamic pressure 0,02 MPa (0,2 bar) min. 0,1 MPa P 0,5 MPa (1 bar P 5,0 bar) Static pressure 1 MPa (10 bar) max. Hot water inlet temperature T 90 C 60 C T 80 C Cold water inlet tempe
29、ratures T 25 C T 25 C Distribution (outlet) temperature 45 C T 65 C 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced doc
30、ument (including any amendments) applies. EN 1092-3, Flanges and their joints Circular flanges for pipes, valves, fittings and accessories, PN desig- nated Part 3: Copper alloy flanges EN 1254-1, Copper and copper alloys Plumbing fittings Part 1: Fittings with ends for capillary soldering or capilla
31、ry brazing to copper tubes EN 1254-2, Copper and copper alloys Plumbing fittings Part 2: Fittings with compression ends for use with copper tubes EN 1254-3, Copper and copper alloys Plumbing fittings Part 3: Fittings with compression ends for use with plastics pipes EN 1254-4, Copper and copper allo
32、ys Plumbing fittings Part 4: Fittings combining other end connections with capillary or compression ends EN 1254-5, Copper and copper alloys Plumbing fittings Part 5: Fittings with short ends for capillary braz- ing to copper tubes EN 1982, Copper and copper alloys Ingots and castings EN 12164, Copp
33、er and copper alloys Rod for free machining purposes EN 12165, Copper and copper alloys Wrought and unwrought forging stock EN 13959, Anti-pollution check valves DN 6 to DN 250 inclusive family E, Types A, B, C and D Licensed Copy: London South Bank University, South Bank University, 16/11/2008 11:2
34、7, Uncontrolled Copy, (c) BSI BS EN 15092:2008 EN 15092:2008 (E) 6 EN ISO 228-1, Pipe threads where pressure-tight joints are not made on the thread Part 1: Dimensions, tolerances and designation (ISO 228-1:2000) EN ISO 3822-1, Acoustics Laboratory tests on noise emission from appliances and equipme
35、nt used in water supply installations Part 1: Method of measurement (ISO 3822-1:1999) EN ISO 3822-3, Acoustics Laboratory tests on noise emission from appliances and equipment used in water supply installations Part 3: Mounting and operating conditions for in-line valves and appliances (ISO 3822-3:1
36、997) EN ISO 6509, Corrosion of metals and alloys Determination of dezincification resistance of brass (ISO 6509:1981) ISO 7-1:1994, Pipe threads where pressure-tight joints are made on the threads Part 1: Dimensions, toler- ances and designation 3 Terms and definitions For the purposes of this docum
37、ent, the following terms and definitions apply. 3.1 tempering valve temperature activated valve which mixes hot and cold water to achieve a pre-determined outlet temperature and which is fitted between the water heater and the point of use to control the distribution temperature to be- tween 45 C an
38、d 65 C 3.2 maximum distribution temperature maximum hot water outlet temperature at which the tempering valve is designed to be used and which is 65 C; national regulations may set a lower value distribution temperature 3.3 minimum distribution temperature 45 C which is the minimum hot water outlet
39、temperature at which the tempering valve is designed to be used 3.4 pre-set temperature temperature as set by the manufacturer of the valve 3.5 set temperature distribution temperature between 45 C to 65 C 3.6 adjustable valve valve with a control mechanism which enables the distribution temperature
40、 to be adjusted from one set point to another set point within a pre-determined minimum and maximum value 3.7 temperature override function facility for temporary use, that allows a temperature in excess of the normal distribution temperature of 65 C to enter the hot water distribution system for th
41、ermal disinfection to control the growth of bacteria 3.8 Type 1 tempering valve non-adjustable tempering valve with pre-set temperature Licensed Copy: London South Bank University, South Bank University, 16/11/2008 11:27, Uncontrolled Copy, (c) BSI BS EN 15092:2008 EN 15092:2008 (E) 7 3.9 Type 2 tem
42、pering valve tempering valve adjustable with or without tool and with pre-set temperature 3.10 nominal diameter (DN) nominal diameter referring to the final outlet connection diameter to pipe, of the valve assembly 4 Materials and surface finishes 4.1 General The selection of materials is the respon
43、sibility of the manufacturer, provided they satisfy the following requirements: a) materials and coatings shall not contaminate the potable water, when in normal or accidental contact; b) in a technical document, the manufacturer shall state the nature of the materials and coatings used; c) material
44、 with inadequate corrosion resistance shall have additional protection; d) the materials used shall not deteriorate at a temperature of 95 C for 1 h and be suitable under the temperatures specified in the tests in this European Standard. 4.2 Nature of materials Examples of bronze and brass which may
45、 be used, without coating, for manufacturing purposes are given in Table 2. Licensed Copy: London South Bank University, South Bank University, 16/11/2008 11:27, Uncontrolled Copy, (c) BSI BS EN 15092:2008 EN 15092:2008 (E) 8 Table 2 Examples of copper alloys Material designation Symbol Reference nu
46、mber European Standard CuSn10-C CC480K EN 1982 CuSn5Pb5Zn5-C CC491K EN 1982 CuSn3Zn8Pb5-C CC490K EN 1982 CuZn39Pb3 CW614N EN 12164/EN 12165 CuZn40Pb2 CW617N EN 12164/EN 12165 CuZn36Pb2As CW602N EN 12164/EN 12165 Copper-zinc alloys containing more than 10 % zinc are subject to dezincification when su
47、bmitted to water capable of dezincification. In the countries where the use of products made of dezincification resistant materials is required, the products have to guarantee a dezincification depth of less than 200 m in any direction; they have to be tested in accordance with EN ISO 6509 and have
48、to be marked in compliance with the indications specified in Clause 11, Marking. 5 Design and dimensional requirements 5.1 Backflow prevention Integral backflow prevention devices shall comply with the appropriate standard in their own right. When fitted check valves, they shall comply with the requ
49、irements of EN 13959. 5.2 Dimensional characteristics 5.2.1 General Tempering valves shall be classified by the nominal size (DN) of outlet end connection. 5.2.2 End connections Examples of end connections are given in Table 3. All end connections shall comply with EN 1254. Connec- tions requiring the use of heat to make or break the joint (e.g. capillary) are not permitted directly on the valve body. 5.2.3 Other connections (e.g. unions) Connections, other than those specified in