《BS-EN-60439-2-1993.pdf》由会员分享,可在线阅读,更多相关《BS-EN-60439-2-1993.pdf(18页珍藏版)》请在三一文库上搜索。
1、BRITISH STANDARD BS EN 60439-2:1993 Incorporating Amendment No. 1 Low-voltage switchgear and controlgear assemblies Part 2: Particular requirements for busbar trunking systems (busways) The European Standard EN 60439-2:1993 has the status of a British Standard UDC 621.316.54 Licensed Copy: sheffield
2、un sheffieldun, na, Fri Nov 10 07:38:42 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS EN 60439-2:1993 This British Standard, having been prepared under the direction of the Power Electrical Engineering Standards Committee, was published under the authority of the Board of BSI and comes into effect o
3、n 30 November 1988 BSI 02-1999 First published February 1978 First revision November 1988 The following BSI references relate to the work on this standard: Committee reference PEL/12 Draft for comment 85/33085 DC ISBN 0 580 16978 2 Committees responsible for this British Standard The preparation of
4、this British Standard was entrusted by the Power Electrical Engineering Standards Committee (PEL/-) to Technical Committee PEL/12 upon which the following bodies were represented: ASTA Certification Services Association of British Mining Equipment Companies Association of Supervisory and Executive E
5、ngineers British Gas plc Building Employers Confederation Department of Trade and Industry, Consumer Safety Unit, CA Division Electrical Contractors Association Electrical Installation Equipment Manufacturers Association (BEAMA Ltd) Electricity Supply Industry in England and Wales Engineering Equipm
6、ent and Materials Users Association ERA Technology Ltd GAMBICA (BEAMA Ltd) Health and Safety Executive National Inspection Council for Electrical Installation Contracting Transmission and Distribution Association (BEAMA Ltd) Amendments issued since publication Amd. No.Date of issueComments 7775July
7、1993Indicated by a sideline in the margin Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 07:38:42 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS EN 60439-2:1993 BSI 02-1999i Contents Page Committees responsible Inside front cover National foreword ii 1General3 2Definitions3 3Classification of
8、 assemblies4 4Electrical characteristics of assemblies4 5Information to be given regarding the assembly4 7Design and construction4 8Test specifications5 Appendix F Example of determination of R and X by calculation from measurements for a three-phase a.c. busbar trunking system 9 Annex ZA (normative
9、) Other international publications quoted in this standard with the references of the relevant European publications 10 Annex ZC (normative)11 Publications referred to Inside back cover Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 07:38:42 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS EN 6
10、0439-2:1993 ii BSI 02-1999 National foreword This Part of BS 5486 has been prepared under the direction of the Power Electrical Engineering Standards Committee and supersedes BS 5486-2:1978, which is withdrawn. It is identical with IEC Publication 439-2:1987 “Low-voltage switchgear and controlgear a
11、ssemblies, Part 2: Particular requirements for busbar trunking systems (busways)”, published by the International Electrotechnical Commission (IEC). In 1993 the European Committee for Electrotechnical Standardization (CENELEC) accepted IEC 439-2:1987 as European Standard EN 60439-2:1993. As a conseq
12、uence of implementing the European Standard this British Standard is renumbered as BS EN 60439-2 and any reference to BS 5486-2 should be read as a reference to BS EN 60439-2. This Part of BS 5486 is a supplement to BS 5486-1, which specifies the general requirements for busbar trunking systems. The
13、 following is adapted from the IEC preface. Busbar trunking systems (busways) shall comply with all the general requirements specified in BS 5486-1, unless otherwise indicated in this Part of BS 5486, and shall also comply with the additional particular requirements contained in this Part. This Part
14、 shall be read in conjunction with BS 5486-1. Its clauses and subclauses modify or replace the corresponding clauses of BS 5486-1; their numbering therefore corresponds to the latter. Where there is no corresponding clause or subclause in this Part, the clause or subclause of BS 5486-1 shall apply w
15、ithout modification. Terminology and conventions. The text of the international standard has been approved as suitable for publication as a British Standard without devia- tion. Some terminology and certain conventions are not identical with those used in British Standards. The Technical Committee h
16、as reviewed the provisions of IEC 570, to which reference is made in the text, and has decided that they are acceptable for use in conjunction with this standard. A related British Standard for IEC 570 is BS 4533 “Luminaires” Section 2.6:1979 “Electrical supply track systems for luminaires”. A Briti
17、sh Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible for their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Cross-references International standardCorrespon
18、ding British Standard IEC 439-1:1985BS 5486 Low-voltage switchgear and controlgear assemblies Part 1:1986 Specification for type-tested and partially type-tested assemblies (general requirements) (Identical) Summary of pages This document comprises a front cover, an inside front cover, pages i and i
19、i, the EN title page, pages 2 to 12, an inside back cover and a back cover. This standard has been updated (see copyright date) and may have had amendments incorporated. This will be indicated in the amendment table on the inside front cover. Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 07
20、:38:42 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 60439-2 February 1993 UDC 621.316.54 Descriptors: Low-voltage switchgear and controlgear, assembly, busbar trunking system English version Low-voltage switchgear and controlgear assemblies Part 2:
21、Particular requirements for busbar trunking systems (busways) (IEC 439-2:1987 + A1:1991, modified) Ensembles dappareillage basse tension Deuxime partie: Rgles particulires pour les canalisations prfabriques (CEI 439-2:1987 + A1:1991, modifis) Niederspannung-Schaltgerte-kombinationen Teil 2: Besonder
22、e Anforderungen an Schienenverteiler (IEC 439-2:1987 + A1:1991, modifiziert) This European Standard was approved by CENELEC on 1991-12-10. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a na
23、tional standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version
24、 in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Denmark, Finland, Fran
25、ce, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom. CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Cen
26、tral Secretariat: rue de Stassart 35, B-1050 Brussels 1993 Copyright reserved to CENELEC members Ref. No. EN 60439-2:1993 Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 07:38:42 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 60439-2:1993 BSI 02-1999 2 Foreword The CENELEC questionnaire proced
27、ure, performed for finding out whether or not the International Standard IEC 439-2:1987 could be accepted without textual changes, has shown that some common modifications were necessary for the acceptance as European Standard. The reference document, together with the common modifications prepared
28、by the CENELEC Technical Committee TC 17D, Low-voltage switchgear and controlgear assemblies, and its amendment 1:1991 was submitted to the CENELEC members for formal vote. The text of the draft was approved by CENELEC as EN 60439-2 on 10 December 1991. The following dates were fixed: For products w
29、hich have complied with the relevant national standard before 1993-12-01, as shown by the manufacturer or by a certification body, this previous standard may continue to apply for production until 1998-12-01. As agreed previously, the terms defined in this standard are given in the three official CE
30、NELEC languages (English, French and German), see Annex ZC. Annexes designated “normative” are part of the body of the standard. In this standard, Annex ZA and Annex ZC are normative. Busbar trunking systems (busways) shall comply with all requirements of EN 60439-1:1990, Low-voltage switchgear and
31、controlgear assemblies Part 1: Requirements for type-tested and partially type-tested assemblies, if not otherwise indicated hereinafter and shall also comply with the particular requirements contained in this standard. The clauses of this standard supplement, modify or replace clauses in EN 60439-1
32、. Where there is no corresponding clause or subclause in this standard, the clause or subclause of the main document applies without modification. In view of the fact that this standard should be read in conjunction with EN 60439-1, the numbering of its clauses and subclauses correspond to the latte
33、r. latest date of publication of an identical national standard(dop)1993-12-01 latest date of withdrawal of conflicting national standards(dow)1993-12-01 Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 07:38:42 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 60439-2:1993 BSI 02-19993 1 General
34、1.1 Scope 1.1 Replace the added paragraph by: This standard applies to busbar trunking systems and their accessories. It also applies to busbar trunking systems intended to supply luminaires through tap-off units but does not apply to supply track systems in accordance with EN 60570. 1.2 Add the fol
35、lowing paragraph: The busbar trunking systems considered in this standard are type-tested assemblies (TTA). 2 Definitions 2.1.1.2 Partially type-tested LV switchgear and controlgear assemblies (PTTA) Not applicable. 2.3.4 busbar trunking system (busway) a type-tested assembly in the form of a conduc
36、tor system comprising busbars which are spaced and supported by insulating material in a duct, trough or similar enclosure The assembly may consist of units such as: busbar trunking units with or without tap-off facilities, phase transposition, expansion, flexible, feeder and adapter units, tap-off
37、units. NOTEThe term “busbar” does not prejudge the geometrical shape, size or dimensions of the conductor. Add the following definitions: 2.3.5 busbar trunking unit a unit of a busbar trunking system complete with busbars, their supports and insulation, external enclosure and any fixing and connecti
38、ng means to other units, with or without tap-off facilities NOTETrunking units may have different geometrical shapes such as straight length, elbow, tee or cross. 2.3.6 busbar trunking unit with tap-off facilities a busbar trunking unit designed to enable tap-off units to be installed at one or more
39、 points as predetermined by the manufacturer the connection of tap-off units to the busbar trunking unit may or may not require the busbar system to be disconnected from the supply 2.3.7 busbar trunking unit with trolley-type tap-off facilities a busbar trunking unit designed to permit the use of ro
40、ller- or brush-type tap-off units 2.3.8 busbar trunking adapter unit a busbar trunking unit intended to connect two units of the same system but of different type or of different rated current 2.3.9 busbar trunking expansion unit a busbar trunking unit intended to permit a certain movement in the ax
41、ial direction of the busbar trunking system, e.g. thermal expansion 2.3.10 busbar phase transposition unit a busbar trunking unit intended to change the relative positions of the phase conductors in order to balance the inductive reactances or to transpose the phases (such as L1-L2-L3-N to N-L3-L2-L
42、1) Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 07:38:42 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 60439-2:1993 4 BSI 02-1999 2.3.11 flexible busbar trunking unit a busbar trunking unit having conductors and enclosures designed to be bent during installation 2.3.12 busbar trunking feed
43、er unit a busbar trunking unit serving as any incoming unit. The connection of the feeder unit to the supply may or may not require the supply to be disconnected 2.3.13 tap-off unit an outgoing unit for tapping-off power from the busbar trunking unit with tap-off facilities (see Sub-clause 2.3.6), s
44、uch as rollers, brushes or plug-in devices 3 Classification of assemblies Add as last item: the mechanical loads they can withstand (see Sub-clause 7.1.1). 4 Electrical characteristics of assemblies Add Sub-clause 4.10 as follows: 4.10 Resistance and reactance values The manufacturer shall state in
45、the manner described in Clause 5 the following mean values of the different phases, if any: The values of R and X may be determined by direct measurement or by calculations from measurements (see Appendix F). 5 Information to be given regarding the assembly 5.1 Nameplates Add after the first paragra
46、ph: One nameplate should be located near one end of each busbar trunking unit and one each tap-off unit. r) resistance, reactance and impedance values. 7 Design and construction 7.1.1 General Add the following text: Busbar trunking systems shall be designed as type-tested low-voltage switchgear and
47、controlgear assemblies (TTA). According to the manufacturers indications, busbar trunking systems are intended to withstand: either normal mechanical loads (see Sub-clause 7.1.1.1), or heavy mechanical loads (see Sub-clause 7.1.1.2), or special mechanical loads (see Sub-clause 7.1.1.3). R =the mean
48、ohmic resistance of the trunking system per metre length per phase: for all busbar trunking systems irrespective of rated current: resistance R20 at a conductor temperature of + 20 C; further, for busbar trunking systems with a rated current greater than 630 A: resistance Rt when thermal equilibrium
49、 is reached at an ambient temperature of + 20 C for the rated current. X=the mean reactance of the trunking system per metre length per phase at rated frequency. Licensed Copy: sheffieldun sheffieldun, na, Fri Nov 10 07:38:42 GMT+00:00 2006, Uncontrolled Copy, (c) BSI EN 60439-2:1993 BSI 02-19995 7.1.1.1 Normal mechanical loads For busbar trunking systems, normal mechanical loads include, in addition to their own weight, mechanical loads imposed by the feeder and tap-off units. NOTE 1The necessary mechanical rigidity may be obtained