CGA-S-1.3-2008.pdf
《CGA-S-1.3-2008.pdf》由会员分享,可在线阅读,更多相关《CGA-S-1.3-2008.pdf(35页珍藏版)》请在三一文库上搜索。
1、 CGA S-1.32008 PRESSURE RELIEF DEVICE STANDARDS PART 3STATIONARY STORAGE CONTAINERS FOR COMPRESSED GASES EIGHTH EDITION COMPRESSED GAS ASSOCIATION, INC. 4221 Walney Road, 5th Floor Chantilly, VA 20151 Phone: 703-788-2700 Fax: 703-961-1831 E-mail: PAGE ii COMPRESSED GAS ASSOCIATION, INC. CGA S-1.320
2、08 PLEASE NOTE: The information contained in this document was obtained from sources believed to be reliable and is based on technical information and experience currently available from members of the Compressed Gas Association, Inc. and others. However, the Association or its members, jointly or s
3、everally, make no guarantee of the results and assume no liability or responsibility in connection with the information or suggestions herein contained. Moreover, it should not be assumed that every acceptable commodity grade, test or safety procedure or method, precaution, equipment or device is co
4、ntained within, or that abnormal or unusual circumstances may not warrant or suggest further requirements or additional procedure. This document is subject to periodic review, and users are cautioned to obtain the latest edition. The Associa- tion invites comments and suggestions for consideration.
5、In connection with such review, any such comments or suggestions will be fully reviewed by the Association after giving the party, upon request, a reasonable op- portunity to be heard. Proposed changes may be submitted via the Internet at our web site, . This document should not be confused with fed
6、eral, state, provincial, or municipal specifications or regulations; insurance requirements; or national safety codes. While the Association recommends reference to or use of this document by government agencies and others, this document is purely voluntary and not binding. A listing of all publicat
7、ions, audiovisual programs, safety and technical bulletins, and safety posters is available via the Internet at our website at . For more information contact CGA at Phone: 703-788-2700, ext. 799. E-mail: . Work Item 08-052 Bulk Distribution Equipment and Standards Committee NOTETechnical changes fro
8、m the previous edition are underlined. EIGHTH EDITION: 2008 SEVENTH EDITION: 2005 SIXTH EDITION: 2003 FIFTH EDITION: 1995 2008 The Compressed Gas Association, Inc. All rights reserved. All materials contained in this work are protected by United States and international copyright laws. No part of th
9、is work may be reproduced or transmitted in any form or by any means, electronic or mechanical including photocopying, recording, or any informa- tion storage and retrieval system without permission in writing from The Compressed Gas Association, Inc. All requests for permission to reproduce materia
10、l from this work should be directed to The Compressed Gas Association, Inc., 4221 Walney Road, Suite 500, Chantilly VA 20151. You may not alter or remove any trademark, copyright or other notice from this work. -,-,- CGA S-1.32008 COMPRESSED GAS ASSOCIATION, INC. PAGE iii Contents Page 1 Introductio
11、n.1 2 Scope and purpose1 2.1 Scope 1 2.2 Purpose.1 3 Definitions.1 4 Types of pressure relief devices.4 5 Application requirements for pressure relief devices4 5.1 General4 5.2 Piping of pressure relief systems.9 5.3 Commodity-based requirements .9 5.4 Jacket relief device11 6 Design and constructio
12、n requirements for pressure relief devices.11 6.1 General11 6.2 Flow capacities for conditions other than fire 15 6.3 Flow capacities under fire conditions.16 6.4 Pressure relief valves18 6.5 Nonreclosing devices 19 6.6 Nonreclosing device in combination with a pressure relief valve 19 6.7 Breaking
13、pin devices in combination with a pressure relief valve19 7 Tests of pressure relief devices19 7.1 Pressure tests of pressure relief valves.19 7.2 Flow capacity tests of pressure relief valves.19 7.3 Test of pressure relief devices other than pressure relief valves 20 7.4 Rejected material.20 8 Iden
14、tification .20 9 Maintenance requirements for pressure relief devices.20 10 References.21 11 Additional references22 Tables Table 1Minimum required working pressures and values of Gi and Gu for commonly used flow rating pressures in U.S. customary units23 Table 2Minimum required working pressures an
15、d values of Gi and Gu for commonly used flow rating pressures in metric units.24 Table 3Thermal conductivity for refrigerated (cryogenic fluids) at the mean temperature between saturation and 1200 F at 14.7 psia (649 C at 101.325 kPa abs) 30 Table 4Constant C for gas or vapor related to ratio of spe
16、cific heats (k = Cp/Cv) at 60 F and 14.696 psia (15 C and 101.325 kPa abs).30 Table 5Saturation temperature, compressibility factor and average specific heat for common gases at selected flow rating pressures.31 -,-,- This page is intentionally blank. CGA S-1.32008 COMPRESSED GAS ASSOCIATION, INC. P
17、AGE 1 1 Introduction This part of the Pressure Relief Device Standards presents the minimum requirements recommended by the Compressed Gas Association, Inc. (CGA), for pressure relief devices (PRDs) being used on compressed gas storage containers constructed in accordance with the American Society o
18、f Mechanical Engineers ASME Boiler and CGA G-2.1, American National Standard Safety Requirements for the Storage and Handling of Anhydrous Ammonia (ANSI K61.1) 4. A number of states and cities have pressure vessel laws and regulations that include requirements for PRDs. Manufacturers and users are c
19、autioned that in some instances the relief devices recommended in this standard might not be acceptable unless special permission is obtained from the authority having jurisdiction. 2.2 Purpose The purpose of this standard is to complement the requirements of various regulations, codes, standards, o
20、r specifications applicable to storage containers for compressed gases. In case of conflict, the requirements of the regulations, codes, standards, or specifications of the authorities having jurisdiction over such containers shall apply. It is recommended that containers fabricated after December 3
21、1, 1995, use PRDs that meet the requirements of this edition of CGA S-1.3. CGA believes that reclosing PRDs on a container shall be able to handle all operational emergency conditions except fire and liquid displacement from a runaway fill. Where fire or liquid overfill is a credible emergency event
22、, reclosing or nonreclosing PRDs shall be provided. 3 Definitions For the purpose of this standard, the following definitions apply. 3.1 ASME Code Paragraph U-68, U-69, U-200, or U-201 of Section VIII of the Boiler and Pressure Vessel Code, 1949 Edition; or Section VIII of the Boiler and Pressure Ve
23、ssel Code, 1950 edition through the current edition, including ad- denda 1. 3.2 Combination pressure relief device Breaking pin device in combination with a pressure relief valve in which the breaking pin device is located between the container and the pressure relief valve; 1 References are shown b
24、y bracketed numbers and are listed in order of appearance in the reference section. 2 kPa shall indicate gauge pressure unless otherwise noted as (kPa, abs) for absolute pressure or (kPa, differential) for dif- ferential pressure. All kPa values are rounded off per CGA P-11, Metric Practice Guide fo