《BS-6195-1993.pdf》由会员分享,可在线阅读,更多相关《BS-6195-1993.pdf(20页珍藏版)》请在三一文库上搜索。
1、BRITISH STANDARD BS 6195:1993 Incorporating Amendment No. 1 Specification for Insulated flexible cables and cords for coil leads UDC 621.315.21 + 621.315.342:621.3.045.6 Licensed Copy: sheffieldun sheffieldun, na, Tue Dec 05 06:57:52 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS 6195:1993 This Briti
2、sh Standard having been prepared under the direction of the Cables and Insulation Standards Policy Committee, was published under the authority of the Standards Board and comes into effect on 15 May 1993 BSI 07-1999 First published December 1969 Second edition May 1993 The following BSI references r
3、elate to the work on this standard: Committee reference CIL 20 Draft for comment 92 25663 DC ISBN 0 580 22033 8 Committees responsible for this British Standard The preparation of this British Standard was entrusted by the Cables and Insulation Standards Policy Committee (CIL/-) to Technical Committ
4、ee CIL 20, upon which the following bodies were represented: Aluminium Federation Association of Consulting Engineers Association of Manufacturers of Domestic Electrical Appliances British Approvals Service for Cables British Cable Makers Confederation British Plastics Federation British Steel Indus
5、try Department of the Environment (Property Services Agency) Department of Trade and Industry (Consumer Safety Unit, CA Division) Electricity Association Engineering Equipment and Materials Users Association Institution of Electrical Engineers London Regional Transport The following bodies were also
6、 represented in the drafting of the standard, through subcommittees and panels: Association of Manufacturers Allied to the Electrical and Electronic Industry (BEAMA Ltd.) British Electrical Systems Association (BEAMA Ltd.) British Non-Ferrous Metals Federation British Steel plc Chartered Institution
7、 of Building Services Engineers ERA Technology Ltd. Electrical Installation Equipment Manufacturers Association (BEAMA Ltd.) Engineering Industries Association GAMBICA (BEAMA Ltd.) Institution of Incorporated Executive Engineers Lighting Industry Federation Ltd. London Underground Ltd. National Asso
8、ciation of Lift Makers Portable Electric Tool Manufacturers Association Transmission and Distribution Association (BEAMA Ltd.) Amendments issued since publication Amd. No.DateComments 8268November 1994 Indicated by a sideline in the margin Licensed Copy: sheffieldun sheffieldun, na, Tue Dec 05 06:57
9、:52 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS 6195:1993 BSI 07-1999i Contents Page Committees responsible Inside front cover Foreword ii 1 Scope1 2 References1 3 Definitions1 4 Voltage categories1 5 Conductor1 6 Insulation2 7 Cable identification6 8 Marking7 9 Construction and overall dimensions
10、7 10 Schedule of tests7 11 Test conditions8 12 Routine tests8 13 Regular sample tests8 14 Type tests9 Annex A (informative) Guide to use10 Annex B (normative) Method of measuring the surface resistivity of semi-conducting tape10 Annex C (normative) Colour durability12 Annex D (normative) Electrical
11、tests12 Annex E (normative) Performance requirements12 Figure B.1 Method of measuring the surface resistivity of semi-conducting tape11 Table 1 Voltage categories1 Table 2 Concentric strands1 Table 3 Schedule of tests2 Table 4 Type 3, 90 C oil resisting and flame retardant rubber insulated coil lead
12、3 Table 5 Type 4, 90 C flame retardant composite rubber insulated coil lead 4 Table 6 Type 5, 180 C silicone rubber insulated coil lead5 Table 7 Type 9, 125 C flame retardant insulated coil lead6 Table 8 Type 10, 150 C flame retardant insulated coil lead6 Table 9 Routine tests8 Table 10 Regular samp
13、le tests8 Table 11 Type tests8 Table A.1 Typical coil end lead selection10 Table C.1 Temperatures for colour durability test 12 Table D.1 Spark test voltages12 Table E.1 Diameters of mandrels for performance (bend) tests13 Table E.2 Test voltages for performance tests13 Table E.3 Temperatures for ef
14、fect of heating performance test13 Table E.4 Varnish grade 13 List of references Inside back cover Licensed Copy: sheffieldun sheffieldun, na, Tue Dec 05 06:57:52 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS 6195:1993 ii BSI 07-1999 Foreword This edition of BS 6195 has been prepared under the direc
15、tion of the Cable and Insulation Standards Policy Committee at the request of the British Cable Makers Confederation. It supersedes BS 6195:1969 which is withdrawn. This edition introduces two new cable types, type 9 and type 10, and removes four cable types, type 1a, type 1b, type 7 and type 8. Thi
16、s edition introduces these changes in order to bring this standard up to date. There is currently no published international or European standard for cables contained in this British Standard. Product certification. Users of this British Standard are advised to consider the desirability of third par
17、ty certification of product conformity with this British Standard based on testing and continuing surveillance which may be coupled with assessment of a suppliers quality systems against the appropriate Part of BS 5750. Enquiries as to the availability of third party certification schemes are forwar
18、ded by BSI to the Association of Certification Bodies. If a third party certification scheme does not already exist, users should consider approaching an appropriate body from the list of Association members. A British Standard does not purport to include all the necessary provisions of a contract.
19、Users of British Standards are responsible for their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front cover, pages i and ii, pages 1 to 14, an inside back cover a
20、nd a back cover. This standard has been updated (see copyright date) and may have had amendments incorporated. This will be indicated in the amendment table on the inside front cover. Licensed Copy: sheffieldun sheffieldun, na, Tue Dec 05 06:57:52 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS 6195:1
21、993 BSI 07-19991 1 Scope This British Standard specifies requirements for various types of insulation, voltage categories and dimensions for a standard range of insulated flexible cables and flexible cords, which are intended to be connected directly and permanently to a coil winding or other compon
22、ent of electric apparatus. The types of cable included in the standard are as follows. Guidance on the use of this standard is given in Annex A. 2 References 2.1 Normative references This British Standard incorporates by dated or undated reference, provisions from other publications. These normative
23、 references are cited at the appropriate places in the text and the publications are listed on the inside back cover. For dated references, subsequent amendments to or revisions of any of these publications apply to this British Standard only when incorporated in it by amendment or revision. For und
24、ated references, the latest edition of the publication referred to applies. 2.2 Informative references This British Standard refers to other publications that provide information or guidance. Editions of these publications current at the time of issue of this standard are listed on the inside back c
25、over, but reference should be made to the latest editions. 3 Definitions For the purposes of this British Standard, the definitions given in BS 4727-2: Group 08 apply. 4 Voltage categories The flexible cables shall be divided into the voltage categories in Table 1 which are defined by the appropriat
26、e maximum voltage between conductors or between conductor and earth, to which the cable is liable to be subjected during a 1 min test of the equipment to which it is connected. Table 1 Voltage categories 5 Conductor 5.1 The conductor shall be made from tinned, annealed, high conductivity copper wire
27、s as specified in 5.2 or 5.3, except that wires taken from the conductor are not required to pass the tinning test. 5.2 The conductor shall be a class 5 conductor conforming to BS 6360. 5.3 If required, concentric strands shall be used for the sizes stated in Table 2. The number of wires shall be as
28、 stated in Table 2 and the maximum conductor resistance shall be the same for a class 5 conductor of equal area in BS 6360. Table 2 Concentric strands Designated temperature a) Type 3 cable, voltage categories A, C and D. Oil resisting and flame retardant rubber insulated coil leads. 90 C b) Type 4
29、cable, voltage categories A, C, D, E and F. Flame retardant rubber insulated coil leads. 90 C c) Type 5 cable, voltage categories A, C, D, E and F. 180 C silicone rubber insulated coil leads. 180 C d) Type 9 cable, voltage category A. 125 C flame retardant insulated coil leads. 125 C e) Type 10 cabl
30、e, voltage category A. 150 C flame retardant insulated coil leads. 150 C Voltage categoryMaximum equipment test voltage (a.c., r.m.s.) kV A C D E F 2.5 4.0 9.5 17 27 Nominal cross-sectional area Specified number of wires mm2 0.5 0.75 1.0 1.5 2.5 4.0 7 19 19 19 37 37 Licensed Copy: sheffieldun sheffi
31、eldun, na, Tue Dec 05 06:57:52 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS 6195:1993 2 BSI 07-1999 5.4 If required, a tape or tapes shall be applied over the conductor. In the case of voltage categories E and F, if a tape is used it shall be a semi-conducting tape consisting of a textile fabric pr
32、oofed with a suitable semi-conducting compound with a surface resistivity not exceeding 100 000 7 per square. Conformity shall be checked by the test method described in Annex B. 6 Insulation 6.1 Types of insulation The insulation shall meet the requirements stated for each cable type as follows. a)
33、 Type 3 cable. The insulation shall conform to BS 7655-1.4 for type OR 1 compound. b) Type 4 cable. The composite insulation shall conform to BS 7655-1.5 for type FR 1 compound for voltage categories A and C, and type FR 2 compound for voltage categories D, E and F. c) Type 5 cable. The insulation s
34、hall conform to BS 7655-1.1 for type EI 2 compound. d) Type 9 cable. The insulation shall conform to BS 7655-1.6 for type CL 1 compound. e) Type 10 cable. The insulation shall conform to BS 7655-1.6 for type CL 2 compound. Conformity shall be checked by carrying out the appropriate tests listed in T
35、able 3. 6.2 Application The insulation shall be applied closely to the conductor or conductor taping. It shall be possible to remove the insulation without damage to the insulation itself, the conductor or the tin coating. In the case of type 4 cable, there shall be no voids between the composite la
36、yers of insulation which shall be continually adherent. Conformity shall be checked by visual examination and by a manual test. 6.3 Thickness The mean value of the thickness of the insulation shall be not less than the value given for each type, voltage category and cross section of cable in Table 4
37、 to Table 8, as appropriate. In the case of type 4 cable, the thickness of the outer layer of the composite insulation shall be the following percentage of the total thickness of the insulation: a) for voltage categories A, C, D and E: 25 % to 50 % b) for voltage category F: 20 % to 35 % NOTEFor all
38、 types of cable, it is permissible for the thickness at any place to be less than the value specified provided that the difference does not exceed 0.1 mm + 10 % of the value specified. Table 3 Schedule of tests TestRequirements given in clause Test method Category Conductor Construction5BS 6360RS In
39、sulation Material6.1BS 7655T Application6.2Visual examinationRS Thickness6.38.1 of BS 6469-1.1:1992RS Identification7Visual examinationRS Tests on complete cables Cable marking8Visual examination and measurementR Conductor resistance13.2BS 6360RS Voltage test13.3Annex DRS Absence of faults on insula
40、tion 12.2Annex DR Overall dimensions98.3 of BS 6469-1.1:1992RS Colour durability7.3Annex CT Bend test14.2Annex ET Heating test14.3Annex ET Solvent resistance test14.4Annex ET Varnish resistance test14.5Annex ET Fire test14.6BS 4066-1T Licensed Copy: sheffieldun sheffieldun, na, Tue Dec 05 06:57:52 G
41、MT+00:00 2006, Uncontrolled Copy, (c) BSI BS 6195:1993 BSI 07-19993 Table 4 Type 3, 90 C oil resisting and flame retardant rubber insulated coil lead Construction Tinned annealed copper conductor conforming to clause5 Thermosetting insulation conforming to 6.1 Colours for core identification Not spe
42、cified Nominal cross-sectional area of conductor Radial thickness of insulationMean overall diameter (upper limit) Voltage categoryVoltage category ACDACD mm2mmmmmmmmmmmm 0.5 0.75 1.0 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 0.8 0.8 0.8 0.8 0.9 1.0 1.0 1.2 1.4 1.4 1.4 1.4 1.4 1.4 1.5
43、 1.5 1.5 1.6 1.6 1.7 1.8 2.0 2.2 2.3 2.4 2.4 2.6 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.3 3.5 3.7 4.0 4.6 5.4 6.5 7.9 4.5 4.7 4.9 5.2 5.6 6.3 7.5 8.5 9.6 11.4 12.8 14.8 17.2 19.7 21.9 24.1 26.3 28.3 33.0 37.4 8.5 9.1 10.3 11.3 12.4 13.8 15.2 17.1 19.2 22.0 23.5 25.5 27
44、.5 30.6 33.8 37.8 Licensed Copy: sheffieldun sheffieldun, na, Tue Dec 05 06:57:52 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS 6195:1993 4 BSI 07-1999 Table 5 Type 4, 90 C flame retardant composite rubber insulated coil lead Construction Tinned annealed copper conductor conforming to clause 5 Therm
45、osetting insulation conforming to 6.1 Colours for core identification Not specified Nominal cross-sectional area of conductor Radial thickness of insulationMean overall diameter (upper limit) Voltage categoryVoltage category ACDEFACDEF mm2mmmmmmmmmmmmmmmmmmmm 0.5 0.75 1.0 1.5 2.5 4 6 10 16 25 35 50
46、70 95 120 150 185 240 300 400 0.8 0.8 0.8 0.8 0.9 1.0 1.0 1.2 1.4 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.5 1.6 1.6 1.7 1.8 2.0 2.2 2.3 2.4 2.4 2.6 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 3.3 3.5 3.7 4.0 4.
47、6 5.4 6.5 7.9 4.5 4.7 4.9 5.2 5.6 6.3 7.5 8.5 9.6 11.4 12.8 14.8 17.2 19.7 21.9 24.1 26.3 28.3 33.0 37.4 8.5 9.1 10.3 11.3 12.4 13.8 15.2 17.1 19.2 22.0 23.5 25.5 27.5 30.6 33.8 37.8 17.2 18.6 20.0 22.1 24.2 26.3 27.8 29.8 32.1 35.1 24.1 25.5 27.3 29.4 31.5 33.3 35.3 37.3 40.3 Licensed Copy: sheffie
48、ldun sheffieldun, na, Tue Dec 05 06:57:52 GMT+00:00 2006, Uncontrolled Copy, (c) BSI BS 6195:1993 BSI 07-19995 Table 6 Type 5, 180 C silicone rubber insulated coil lead Construction Tinned annealed copper conductor conforming to clause 5 Thermosetting insulation conforming to 6.1 Colours for core id
49、entification Not specified Nominal cross-sectional area of conductor Radial thickness of insulationMean overall diameter (upper limit) Voltage categoryVoltage category ACDEFACDEF mm2mmmmmmmmmmmmmmmmmmmm 0.5 0.75 1.0 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 0.8 0.8 0.8 0.8 0.9 1.0 1.0 1.2 1.4 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.5 1.6 1.6 1.7 1.8 2.0 2.2 2.3 2.4 2.4 2.6 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 7.6 7.6 7.6 7.6 7.6 7