1、 . UL SUBJECT*277A Ba 7275775 05277b3 13T . NOVEMBER, 1988 1 Subject 299A Outline Of Investigation Portable Dry Chemical Extinguishing System Units Issue Number: 2 NOVEMBER, 1988 COPYRIOHT 0 1990.1991 UNDERWRITERS LABORATORIES INC. ULIS Outlines of investigation are copyrighted to protect ULs public
2、ation rights, notto restrict their use in product design or evaluation. Copyright Underwriters Laboratories Inc. Provided by IHS under license with ULLicensee=North Carolina State University/5618801100 Not for Resale, 10/21/2006 22:37:51 MDTNo reproduction or networking permitted without license fro
3、m IHS -,-,- UL SUBJECT*299A 88 9275795 05297611 076 = CONTENTS FOREWORD INlRODUCTION 1 scope 5 CONSTRUCTION 2 AcsemMy . 5 PERFORMANCE 3 Fire Test . Portable Extinguisher Rating . 5 4 Fire Test . Total Fiooding Evaluation . 5 5 Response Test Of Heat Actuating Device 6 6 OperaUngTemperatureTest . 6 Co
4、pyright Underwriters Laboratories Inc. Provided by IHS under license with ULLicensee=North Carolina State University/5618801100 Not for Resale, 10/21/2006 22:37:51 MDTNo reproduction or networking permitted without license from IHS -,-,- - _ _ _ _ _ _ _ _ _ UL SUBJECT*299A 88 9275795 0529765 TO2 = 4
5、 PORTABLE DRY CHEMICAL. EXTINGUicH1NG SYSTEM UNITS - SU 299A NOVEMBER, 1S6 A. This Outline of Investigation contains basic requirements for products covered by Underwriters Laboratories Inc. (UL) under its Fdlow-Up Service for this category within the limitations given betow and in the Scope section
6、 of this Outline o f Investigation. They are subject to revision as further experience and investigation may show is necessary o r desirable. B. conditions of the continued coverage of the manufacturers product. The observance of t h e s e requirements by a manufacturer is one o f the C . A product
7、which complies with the tex& of this Outline of Investigation will not necessary be judged to comply with the Outline of Investigation if, when examined and tested, it is found to have other features which impair the levei of safety contemplated by these requirements. D. A product employing material
8、s or having forms of construction differing from those detailed in the requirements of this Outline of Investigation may be examined and tested according to the intent of the requirements and, if found to be substantially equivalent, may be judged to comply with the Outline of Investigation. E. Ul,
9、in performing its functions in accordance with its objectives, does not assume or undertake to discharge any responsibility of the manufacturer or any other party. The opinions and findings of UL represent its professional judgment given with due consideration to the necessary limitations of practic
10、al operation and state of the a r t at the time of Outline of Investigation is processed. UL shall not be responsible to anyone for the use of or reliance upon this Outline of Investigation by anyone. UL shall not incur any obligation or liability for damages, including consequential damages, arisin
11、g out of o r in connection with the use, interpretation of, or reliance upon this Outline of Investigation. F. Many tests required by the Outline of Investigations of UL are inherently hazardous and adequate safeguards for personnel and property shall be employed in conducting such tests. Copyright
12、Underwriters Laboratories Inc. Provided by IHS under license with ULLicensee=North Carolina State University/5618801100 Not for Resale, 10/21/2006 22:37:51 MDTNo reproduction or networking permitted without license from IHS -,-,- UL SUBJECT*299A 88 W 9275795 O529766 949 1988 PORTABLE DRY CHEMICAL EX
13、TINGUISHING SYSTEM UNITS - SU 2SA 5 INTRODUCTION 1 scope 1 .i These requirements are intended to supplement the Standard for Dry Chemical Fire Extinguishers, UL 2 9 9 , for Portable Dry Chemical Fire Extinguishing System Units provided with a heat responsive automatic means of actuation. These devic
14、es are also to be manually operated as a portable dry chemical fire extinguisher. CONSTRUCTION 2 Assembly 2 . 1 PortaMe dry chemical extinguishing system units are to be provided with both an automatic means of opefation when exposed to an abnormal tise in the endosure ambient temperature and a manu
15、al means of operation when the unit is to be used as a portaMe fire extinguisher. PERFORMANCE 3 F m Test - Portable Extinguisher Rating 3.1 PortaMe dry chemicalexinguishing system units shall be fire tested and rated in accordance with the Standard for the Rating and Fire Testing of Fire Extinguishe
16、rs, UL 71 1 , when manually operated as a portable fire extinguisher. Units obtaining not more than 10 Ib of dry chemical extinguishing agent may be provided with a fixed discharge nozzle in lieu of a discharge hose assembly. 4 Fire Test - Total Flooding Evaluation 4.1 PortaMe dry chemical extinguis
17、hing system units shall totally flood an enclosure and extinguish the testfires in accordance with the requirements of Pars. 4.2 through 4.5 after the unit is conditioned at its speciffed minimum storage temperature for a period of at least 16 h. 4.2 portable extinguishing system unit 4.3 are to be
18、conducted as fdlows: An endosure is to be constructed having the maximum dimensions and vdume specified for the Fire tests incorporating wood cribs, shredded paper, excelsior or heptane, or combinations thereof a) b) c) d) 1-A wood crib centered in the endosure 1-A wood crib offset in the endosure 3
19、.5 Ib of shredded paper centered and a 2.5 ff pan of heptane offset in the enclosure 3.5 Ib o f shredded paper offset and a 2Sf? pan of heptane centered in the endosure e) f) g) 4 Ib of exceisior centered and a 2.5 f? pan of heptane offset in the enclosure 4 Ib of excelsior offset and a 2.5 f? pan o
20、f heptane centered in the enclosure 2.5 # pan of heptane centered in the enclosure h) 2.5 # pan of heptane offset in the endosure Copyright Underwriters Laboratories Inc. Provided by IHS under license with ULLicensee=North Carolina State University/5618801100 Not for Resale, 10/21/2006 22:37:51 MDTN
21、o reproduction or networking permitted without license from IHS -,-,- - - UL SUBJECT*299A B B m 9275795 O529767 885 m 6 #WITABLE DRY CHEMICAL ocI1NGUISiiING SY!SlEM UNTTS - Su 29SA NOVEMBER, 1988 4 . 4 The IA wood crib is to be constructed as described in the Standard for the Rating and Fire Testing
22、 of Fire Extinguishers, UL 7 1 1 . Specifications for excelsior, heptane and the 2.5p test pan are also contained in UL 7 1 1. The term cent& means the center of the floor of the endosure. The term offset means the midpoint between the center of the room and one comer. 4.5 During each fire test, cyl
23、indrical containers having dimensions of 3 in. I D and 4 in. high containing 2 in. of heptane are to be located 2 in. from the comers of test endosures and lacated vertically 1 2 In. below the ceiling of the endosure. The heptane in the these cylinders is to be ignited ater which the other test fuel
24、s (Par. 4 . 3 ) are to be ignited. 5 Response Test 01 Heat Actuating Device 5 . 1 2 min a f t e r the test fue4 is ignition. A portable type extinguishing system unit shall extinguish the heptane fire specified in Par. 5 . 2 within 5 . 2 comer of the test enclosure described in Sec. 4. The heptane I
25、s to be contained in 2-1/2 ( 0 . 2 3 m2) square pan located within 2 in. (50.8mm) of a 5 . 3 air. The test endosure is to have Wo wail openings having an area of 1 f? each to provide combustion 6 Operating Temperature Test 6 . 1 operate within a range o f 13-1/2 percent of the dements marked tempera
26、ture rating. When subjected to the path test described in Pars. 6 . 2 through 6 . 7 , heat responsive element shall 6 . 2 requirements o f Par. 6 . 1 . Ten heat responsive elements are to be subjected to this test and each sample shall comply with the 6 . 3 The heat responsive elements are to be pla
27、ced in an upright position under a load equal to the units design operating load and completely immersed in a liquid bath. The water vessel is to be provided with a source for heating the liquid at the prescribed rate with the means to agitate the liquid and measure the temperature of the liquid bat
28、h. 6 . 4 tested in an o having a flash point exceeding the elements rated temperature. Water is to be used for heat responsive elements having temperature ratings of 175F are to be bath 6.5 An agitator is to be used for obtaining uniformity and temperature of the bath liquid. 6.6 A laboratory mercur
29、y. thermometer, calibrated in accordance with the specifications for ASTM thermometers, ASTM Elm, is to be used to determine temperatures of the liquids used in bath tests. The bulb of a thermometer is to be located level with the heat responsive element. 6 . 7 The temperature o f the bath liquid is
30、 to be raised until the liquid is within 20F (11C) of the temperature o f the heat responsive element for temperature rating of 300F or less and within 30F (1PC) for an element having a temperature rating of 325F (163C) and higher. The rate o f temperature rise is to be controlled at a rate not exce
31、eding 1F (0.5“C) per minute until operation or until a temperature 20F (1 1C) above the rated temperature is reached. The temperature of the liquid and the time of operation, as each heat responsive element operates, are to be recorded. Copyright Underwriters Laboratories Inc. Provided by IHS under license with ULLicensee=North Carolina State University/5618801100 Not for Resale, 10/21/2006 22:37:51 MDTNo reproduction or networking permitted without license from IHS -,-,-