1、Subjects 96 (96A) (in reply, refer to Subject 96) 12 Laboratory Drive Research Triangle Park, NC 27709 October 21, 2004 TO: Standards Technical Panel (STP) for Lightning Protection Systems, STP 96 Subscribers to ULs Standards Services for Lightning Protection Components, UL 96 Installation Requireme
2、nts for Lightning Protection Systems, UL 96A Other Interested Parties SUBJECT: Report of the Meeting of the Standards Technical Panel of UL for Lightning Protection Systems; Request for Comments on the Proposed Requirements for the Fifth Edition of the Standard for Lightning Protection Components, U
3、L 96 and the Twelfth Edition of the Standard for Installation Requirements for Lightning Protection Systems, UL 96A; PROPOSED EFFECTIVE DATES Summary of Topics The following topics were discussed at the meeting: UL 96A 1.96A And NFPA 780 Comparison And Need 2. Section II - Metal Bodies Requiring Bon
4、ding 3. Section 13 - Antennas And Service Entrance (Surge Suppression) 4. Pool Enclosures 5. Additional Items UL 96 6. Comments from the Proposed New Edition bulletin dated February 23, 2004 COMMENTS DUE: NOVEMBER 22,2004 A meeting of the Standards Technical Panel of UL for Lightning Protection Syst
5、ems was held September 9 or buildings of any height that have a structural steel frame that may be substituted for lightning down conductors. 4.5 CLASS II MODIFIED COMPONENTS - Components constructed for use in a system to protect a heavy duty stack. 4.6 CONDUCTOR - The portion of a lightning protec
6、tion system intended to carry the lightning discharge between air terminals and ground. a) Main Conductor - A conductor that interconnects air terminals and serves as a down lead to ground. b) Secondary Conductor - A conductor that connects metal bodies to the lightning protection system to eliminat
7、e the buildup of an electrical potential between them during a lightning strike. 4.7 HEAVY-DUTY STACK - A smoke or vent stack that is more than 75 feet (23 m) high and has a flue with a cross sectional area greater than 500 square inches (0.3 m2). Copyright Underwriters Laboratories Inc. Provided by
8、 IHS under license with ULLicensee=IHS Employees/1111111001, User=Wing, Bernie Not for Resale, 04/02/2007 01:07:49 MDTNo reproduction or networking permitted without license from IHS -,-,- SUBJECT 96 Base end thread diameter inch (mm) -A3- Wall thickness Cross-Sectional inch (mm) inch2 (mm)2 areaa O
9、CTOBER 21, 2004 CONSTRUCTION CLASS I COMPONENTS 5 General 5.1 Class I components shall be made of copper, copper alloy, or aluminum, unless otherwise required in this Standard, as outlined below: a) Copper conductor of the grade ordinarily required for commercial electrical work, generally designate
10、d as being of 95 percent conductivity when annealed. b) A copper alloy as resistant to corrosion as copper under similar conditions. c) Aluminum conductors of electrical grade aluminum. 6 Air Terminals 6.1 An air terminal may be of one piece construction or may have several separate parts including:
11、 point (tip portion), elevation conductor, and base support. 6.2 An air terminal shall not be less than 10 inches (254 mm) long and shall comply with the requirements in Table 6.1. Table 6.1 Minimum air terminal dimensions Material Construction Copper and Solid copper alloy Tubular Aluminum Solid +
12、Tubular Diametera inch (mm) 318 (9.5) 518 (15.9) 112 (12.7) 518 (15.9) (9.5) 0.110 (12.7) 0.196 (126) a The minimum diameter and minimum cross-sectional area are to be determined by measurements taken at various points along the axis of the air terminal for a distance not to exceed 50 percent of the
13、 total length of the air terminal measured from the threaded or base end and exclusive of the threaded portion or adapter of a tubular air terminal. 6.3 A copper or copper alloy air terminal intended for use on a chimney shall be protected from corrosion by tin or lead coating. 6.4 Each air terminal
14、 shall be provided with an integral base support or with not less than five full threads for attachment to the base support. 6.5 The threaded portion of an internally threaded air terminal shall have a minimum wall thickness of 1/16 inch (1.6 mm), measured at the base of the threads. Copyright Under
15、writers Laboratories Inc. Provided by IHS under license with ULLicensee=IHS Employees/1111111001, User=Wing, Bernie Not for Resale, 04/02/2007 01:07:49 MDTNo reproduction or networking permitted without license from IHS -,-,- SUBJECT 96 -A4- OCTOBER 21, 2004 Material Copper or copper alloy Aluminum
16、6.6 A tubular air terminal shall be provided with a threaded adapter for attachment to the base support. The threaded adapter shall comply with the requirements in 6.4 and Table 6.1 with respect to minimum thread size, and shall be securely attached to the air terminal. Minimum thickness Constructio
17、n inch (mm) Cast 3/32 (2.4) Cast 3/32 (2.4) Stamped 0.061 (1.55) Stamped 0.097 (2.46) 6.7 The wind-resistance area of an ornament or decoration on a freestanding, un-braced air terminal shall not exceed 20 square inches (130 cm2) in any plane. For example: A ball 5 inches (127 mm) or less in diamete
18、r complies with this requirement. 7 Air Terminal Base Supports 7.1 The thickness of an air terminal base support shall not be less than the applicable value specified in Table 7.1. Table 7.1 Thickness of air terminal base supports 7.2 A threaded hub provided for the attachment of the air terminal sh
19、all have at least five full threads and, if internally threaded, shall have a wall thickness of not less than 1/16 inch (1.6 mm) measured at the base of the threads. 7.3 A threaded hub is not required on a base support for a construction in which the air terminal is secured by a locknut on each side
20、 of the base support. 7.4 Each base support shall incorporate a connector fitting for connection to the lightning conductor. The conducting cross-sectional area of the base support, between the connector and the base of the air terminal, shall be equal to or greater than that of the conductor. The c
21、onductor shall contact the base for not less than 1-1/2 inches (38 mm) on all sides of the cable. Exception: This requirement does not apply to a base support that complies with the Standard for Qualifying Permanent Connections Used in Substation Grounding, IEEE Std. 837. The applicable tests of IEE
22、E Std. 837 shall be conducted with commercially available lightning protection conductors. 7.5 At least two mounting holes that will accept a No. 10 - 24 or larger bolt or screw shall be provided in the support so that it can be permanently and rigidly fastened. 8 Braces 8.1 An air-terminal brace sh
23、all be provided with two, three, or four legs and with one or two air-terminal guides. Copyright Underwriters Laboratories Inc. Provided by IHS under license with ULLicensee=IHS Employees/1111111001, User=Wing, Bernie Not for Resale, 04/02/2007 01:07:49 MDTNo reproduction or networking permitted wit
24、hout license from IHS -,-,- SUBJECT 96 -A5- OCTOBER 21, 2004 Type of conductor Cable Strand Diameter Weight Area 8.2 A brace shall be made of 1/4-inch (6.4-mm) minimum diameter rod of aluminum, coppedcopper alloy, stainless steel or the equivalent. Material Copper 0.045 inch (1.14 rnrn) 0.187 pound/