UL-96A-BULLETINS-2003.pdf
《UL-96A-BULLETINS-2003.pdf》由会员分享,可在线阅读,更多相关《UL-96A-BULLETINS-2003.pdf(14页珍藏版)》请在三一文库上搜索。
1、Subjects 1449 (96A) (In reply, refer to Subject 1449) 12 Laboratory Drive Research Triangle Park, NC 27709 October 14, 2003 TO:Standards Technical Panel (STP) for Surge Protective Devices, STP 1449 Subscribers to ULs Standards Services for: Transient Voltage Surge Suppressors (UL 1449); Installation
2、 Requirements for Lightning Protection Systems (96A); Other Interested Parties SUBJECT:Report of the Meeting of the Standards Technical Panel of UL for Surge Protective Devices; Request for Comments on the Proposed Requirements for the Second Edition of the Standard for Transient Voltage Surge Suppr
3、essors UL 1449; PROPOSED EFFECTIVE DATE SUMMARY OF TOPICS The following topics were discussed at the meeting: 1) Clarifi cations of UL 96A Requirements 2) Abnormal Overvoltage High Current Tests (Section 37) 3) Abnormal Overvoltage High Current Tests as Intermediate Current Levels 4) Limited Current
4、 Abnormal Overvoltage Test 5) Requirements for Receptacle Faceplates with Integral TVSS 6) Miscellaneous Revisions COMMENTS DUE: November 25, 2003 A meeting of the Standards Technical Panel of UL for Surge Protective Devices was held on September 12, 2003 at The Adams Mark Hotel in Dallas, Texas. Th
5、e purpose of the meeting was to discuss revisions for UL 1449. Copyright Underwriters Laboratories Inc. Provided by IHS under license with ULLicensee=Army Northwestern Div./7838506130 Not for Resale, 08/29/2006 10:06:38 MDTNo reproduction or networking permitted without license from IHS -,-,- INSTRU
6、CTIONS You are requested to send comments on the proposed requirements, impact statements, and proposed effective dates to the STP Secretary. Comments should be made in writing and may be sent by fax to 919-316-5623 or by mail to the attention of Byron McMillan at ULs Research Triangle Park office.
7、Comments may also be sent via E-mail to Byron.McM. Please reference all correspondence to Subject UL 1449. Note all comments received are public and may be circulated to others. If you respond by fax or E-mail, please include your full name and company name and address to ensure a reply. Attached as
8、 Appendix A for your review and comment are proposed requirements for UL 1449, Transient Voltage Surge Suppressors. Attached as Appendix B for your review and comment are the impact statements and proposed effective dates. Attached as Appendix C is the STP membership roster. Attached as Appendix D i
9、s information concerning Working Groups. Attached as Appendix E is a table presented during the meeting to compare tests conducted in UL 1449, IEEE C62.34, Standard for Performance of Low-Voltage Surge-Protective Devices (Secondary Arresters), and IEEE C62.11-1993, Standard for Metal-Oxide Surge Arr
10、esters for Alternating Current Power Circuits. Attached as Appendix F is a list of those who attended the meeting. Questions regarding interpretation of requirements should be directed to the responsible UL Staff. Please see Appendix G of this bulletin regarding designated responsibility for the sub
11、ject product categories. Please note that proposed requirements are of a tentative and early nature and are for review and comment only. Current requirements are to be used to judge a product until these requirements are published in fi nal form. * * * * * * The following report is not intended to b
12、e a verbatim transcript of the discussion at the meeting, but is intended to record the signifi cant features of those discussions. MEETING CALL TO ORDER, ANNOUNCEMENTS, INVITATION OF MEMBERS, GUESTS, OBSERVERS John Thompson, Chair of the Standards Technical Panel for Transient Voltage Surge Suppres
13、sors, called the meeting to order at 8:30 A.M. After making announcements and explaining the rules of the meeting, the Chair introduced himself, the outgoing Primary Designated Engineer and the incoming Primary Designated Engineer, and the Secretary. The Chair then asked members to introduce themsel
14、ves. A roster was posted for members to review for accuracy and initial, indicating their presence at the meeting. ANNOUNCEMENTS FROM THE SECRETARY STP BALANCE- The current balance of this STP is 53 percent Producer, 25 percent User, and 22 percent General Interest. ULs goal is equal interest partic
15、ipation. Members were encouraged to provide names of potential general interest and user members to help achieve this goal. OCTOBER 14, 2003SUBJECT 1449-2- Copyright Underwriters Laboratories Inc. Provided by IHS under license with ULLicensee=Army Northwestern Div./7838506130 Not for Resale, 08/29/2
16、006 10:06:38 MDTNo reproduction or networking permitted without license from IHS -,-,- 1. CLARIFICATION OF UL 96A REQUIREMENTS DISCUSSION AND RATIONALE In December 2002 UL issued an industry bulletin under UL 96A, Installation Requirements for Lightning Protection Systems, with a section on Surge Pr
17、otection Clarifi cation. The section stated, TVSS devices that are Listed only under UL 1449, Transient Voltage Surge Suppressors, are not suitable for Lightning protection. As a direct result of this UL 96A bulletin, a review of transient voltage surge suppressors (TVSS) and surge arresters require
18、ments and practice was initiated. Historically, TVSS devices have been installed at the main service entrance (on the load side of the main overcurrent protective device) and on panels and sub panels within a facility. Due to the UL 96A bulletin, facilities with TVSS devices installed, as stated abo
19、ve, were no longer eligible for labeling under the UL Master Label Certifi cation for Lightning Protection Systems. Only facilities where surge arresters are installed are considered eligible for the UL Master Label Certifi cation for Lightning Protection program. This issue was raised and discussed
20、 at the May 16, 2003 STP 1449 meeting in St. Pete Beach Florida and a Working Group (see appendix D) was formed to address it. The working group proposed wording to be incorporated into UL 96A, which would allow TVSS products, located on the load side of the facilities main overcurrent device, to be
21、 used for UL Master Label Certifi cation for Lightning Protection. The wording was circulated internally to the designated engineers at each UL office for comments. The responses indicated that the wording could not be added without additional rationale. Consequently the issue was not resolved prior
22、 to this STP meeting and remained an active agenda item. UL presented a table comparing the tests conducted for secondary surge arresters under C62.11-1993, and C62.34, and for TVSS devices under UL 1449. An expanded table was provided by an STP member and is currently under review by UL staff. This
23、 table will be shared with the Working Group. The objective of this comparative review is to document the testing similarities and differences between these two categories in order to ultimately assess protection equivalency. Once established, a determination can be made regarding the suitable insta
24、llation location of the TVSS device and revision to UL 96A. This information is required in order for Lightning Protection Systems utilizing TVSS devices to be eligible for the UL Master Label Certifi cation for Lightning Protection Systems. Discussion also took place on the historical use of surge