BS-EN-61181-2007.pdf
《BS-EN-61181-2007.pdf》由会员分享,可在线阅读,更多相关《BS-EN-61181-2007.pdf(18页珍藏版)》请在三一文库上搜索。
1、BRITISH STANDARD BS EN 61181:2007 Mineral oil-filled electrical equipment Application of dissolved gas analysis (DGA) to factory tests on electrical equipment The European Standard EN 61181:2007 has the status of a British Standard ICS 29.040.10; 29.180 ? Licensed Copy: London South Bank University,
2、 London South Bank University, Wed May 16 03:55:48 GMT+00:00 2007, Uncontrolled Copy, (c) BSI BS EN 61181:2007 This British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 May 2007 BSI 2007 ISBN 978 0 580 50652 9 National foreword This British Standard
3、 was published by BSI. It is the UK implementation of EN 61181:2007. It is identical with IEC 61181:2007. It supersedes BS EN 61181:1993 which is withdrawn. The UK participation in its preparation was entrusted to Technical Committee GEL/10, Fluids for electrotechnical applications. A list of organi
4、zations represented on this committee can be obtained on request to its secretary. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard cannot confer immunity from legal obligati
5、ons. Amendments issued since publication Amd. No. DateComments Licensed Copy: London South Bank University, London South Bank University, Wed May 16 03:55:48 GMT+00:00 2007, Uncontrolled Copy, (c) BSI EUROPEAN STANDARD EN 61181 NORME EUROPENNE EUROPISCHE NORM April 2007 CENELEC European Committee fo
6、r Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050 Brussels 2007 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members
7、. Ref. No. EN 61181:2007 E ICS 29.040.10; 29.180 Supersedes EN 61181:1993 English version Mineral oil-filled electrical equipment - Application of dissolved gas analysis (DGA) to factory tests on electrical equipment (IEC 61181:2007) Matriels lectriques imprgns dhuile minrale - Application de lanaly
8、se des gaz dissous (AGD) lors dessais en usine de matriels lectriques (CEI 61181:2007) Getrnkte Isolierstoffe - Verwendung der Gasanalyse fr gelste Gase (DGA) als Werksprfung fr elektrische Betriebsmittel (IEC 61181:2007) This European Standard was approved by CENELEC on 2007-03-01. CENELEC members
9、are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application t
10、o the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has t
11、he same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands
12、, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Licensed Copy: London South Bank University, London South Bank University, Wed May 16 03:55:48 GMT+00:00 2007, Uncontrolled Copy, (c) BSI EN 61181:2007 2 Foreword The text of document 10/675/F
13、DIS, future edition 2 of IEC 61181, prepared by IEC TC 10, Fluids for electrotechnical applications, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as EN 61181 on 2007-03-01. This European Standard supersedes EN 61181:1993. EN 61181:2007 includes the following significant
14、 technical changes with respect to EN 61181:1993: the specific procedures used during factory tests (sampling location, sampling frequency, gas extraction and chromatographic analysis in the laboratory) are described in more detail; information is provided in Annex A concerning the residual gas cont
15、ents recommended before thermal tests on power transformers, typical gas values observed during the tests and cases where gas formation during the tests was followed by problems in the transformers; typical values observed during chopped lightning-impulse tests on instrument transformers are indicat
16、ed in Annex B. The following dates were fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2007-12-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2010-0
17、3-01 Annex ZA has been added by CENELEC. _ Endorsement notice The text of the International Standard IEC 61181:2007 was approved by CENELEC as a European Standard without any modification. _ Licensed Copy: London South Bank University, London South Bank University, Wed May 16 03:55:48 GMT+00:00 2007
18、, Uncontrolled Copy, (c) BSI 3 EN 61181:2007 CONTENTS INTRODUCTION.4 1 Scope 5 2 Normative references .5 3 General caution, health, safety and environmental protection 5 4 Oil sampling .6 4.1 General.6 4.2 Sample containers.6 4.3 Sampling location 6 4.4 Sampling frequency.6 4.5 Sample labelling7 4.6
19、 Sample storage .7 4.7 Disposal of waste oil8 5 Factors affecting gassing rate during thermal tests8 6 Dissolved gas extraction and analysis.8 7 Report10 Annex A (informative) Gas formation rates during thermal tests on power transformers .11 Annex B (informative) Gas formation rates during chopped-
20、lightning impulse tests on instrument transformers 6.13 Annex ZA (normative) Normative references to international publications with their corresponding European publications15 Bibliography .14 Table 1 Required detection limits for factory tests.8 Table A.1 Ranges of 90 % typical rates of gas format
21、ion in modern, mineral oil- filled power transformers during thermal tests, in l/l/h.11 Table A.2 Survey of cases followed by problems in core-type, mineral oil- filled power transformers, for various rates of gas formation observed during the thermal tests, (values in l/l/h).12 Table B.1 90 % typic
22、al gas concentration increases observed between the beginning and the end of chopped lightning-impulse tests on instrument transformers13 Licensed Copy: London South Bank University, London South Bank University, Wed May 16 03:55:48 GMT+00:00 2007, Uncontrolled Copy, (c) BSI EN 61181:2007 4 INTRODUC
23、TION IEC technical committee 10, responsible for IEC 61181, has prepared guidelines for performing DGA measurements during factory testing on equipment filled with mineral insulating oil in order to ensure consistency in the industry and improve the confidence with which the results will be used. DG
24、A is used routinely as a standard quality control procedure during and after factory tests on electrical equipment, for example during temperature-rise and chopped lightning-impulse tests, to indicate that a design meets specified requirements. Due to the small quantities of gases generated during f